DSTU-N B V.1.1-27:2010: climatic regions and Tmin for PV strings

In frost, the open-circuit voltage of panels rises. To keep a string below the inverter’s voltage limit you need the site’s lowest air temperature. In Ukraine it comes from the “Building climatology” standard.

Ground frame designer

Design the ground frame for your solar plant

Solispec picks the profiles and posts, checks the frame against snow and wind to the DBN and prices it down to the last bolt.

  • No sign-up
  • Snow and wind check
  • Drawings and estimate

Edition and status

DSTU-N B V.1.1-27:2010 “Building climatology”. Status as of 14.10.2026: in force per the norms register Solispec checked on 04.10.2026.

The official text: UkrNDNC, the national standards body (the standard’s text is sold). Solispec does not host the norm texts. Look for the current edition at the official source.

Why a solar plant needs climatology

DSTU HD 60364-7-712:2022 (Annex B.1) requires UOC MAX to be calculated at the lowest ambient temperature of the installation site, Tmin:

UOC MAX = KU · UOC STC, KU = 1 + αUoc/100 · (Tmin − 25)

Without Tmin or the panel’s temperature coefficient the standard says to take 1.2 · UOC STC. The colder it is, the fewer panels fit in a string. That is why Tmin needs a source rather than a “usual” −25 °C.

Climatic regions: Table 1 and Figure 1

The standard divides Ukraine into climatic regions. For regions I and II, Table 1 gives a range of the absolute minimum: −37…−40 °C and −32…−42 °C. Solispec takes the colder end, so UOC MAX comes out higher, on the safe side.

RegionNameTmin in Solispec
INorth-west−40 °C
IISouth-east−42 °C
IIIACarpathian−38 °C
IIIBTranscarpathian−32 °C
IVSouthern coast of Crimea−20 °C
VCrimean mountains−27 °C

The engine draws the boundary between regions I and II from Figure 1 read by eye, so near it the accuracy is ±0.2–0.3° of latitude. Kyiv is in region I: Tmin = −40 °C.

An example

A hypothetical panel with UOC STC = 49.5 V and α = −0.25 %/K in Kyiv: KU = 1 + (−0.25/100) · (−40 − 25) = 1.1625, UOC MAX ≈ 57.5 V. Without data it would be 1.2 · 49.5 = 59.4 V. For an inverter limited to 1,000 V that is 17 panels per string instead of 16.

How Solispec applies it

The constructor and the string calculator first take the Tmin You entered yourself. If the field is empty, the engine finds the climatic region from the site coordinates and takes its Tmin, with the source in the report: “DSTU-N B V.1.1-27:2010, Table 1”. If no site is set, the 1.2 · UOC STC rule applies.