Glossary · Climate
Site minimum temperature Tmin
The lowest ambient air temperature at the PV site; it sets the maximum open-circuit voltage of a string, U_OC MAX.
Ground frame designer
Design the ground frame for your solar plant
Solispec picks the profiles and posts, checks the frame against snow and wind to the DBN and prices it down to the last bolt.
- No sign-up
- Snow and wind check
- Drawings and estimate
Definition
In DSTU HD 60364-7-712:2022 (Annex B.1), Tmin is the lowest ambient air temperature at the PV installation site. Not a winter average and not the heating design temperature, but the absolute minimum. A panel’s open-circuit voltage rises in frost, so this temperature decides how many panels fit into a string without exceeding the inverter’s voltage limit.
KU = 1 + α/100 · (Tmin − 25)Where the value comes from: in Ukraine, absolute minima are given in DSTU-N B V.1.1-27:2010 (Table 1) by climatic region. For Kyiv (region I) it is −40 °C. Example for an illustrative panel with Uoc = 49.5 V and α = −0.25 %/K: KU = 1 + (−0.25/100)·(−40 − 25) = 1.1625, so in frost one panel gives up to 57.5 V. At −25 °C the same factor would be 1.125 and the voltage 55.7 V; 1.8 V per panel on an 18-panel string adds up to more than 30 V.
If Tmin is unknown, the standard does not let you guess it: UOC MAX is then taken as 1.2·UOC STC. The −25 °C found in older tools and tables is too optimistic for most of Ukraine.
A few practical notes. The standard uses the site's air temperature, not the module's, and the absolute minimum at that. Tmin is only needed for the upper string limit. For the lower end of the MPPT window heat matters instead, and Solispec uses the panel's hot operating voltage there. If you have weather observations near the site with a lower minimum, you can enter them in the Tmin field. Do not use heating design temperatures from other tables: they are not the absolute minimum and are warmer than it. The lower Tmin, the shorter the allowed string, so rounding 'towards warm' always works against safety.
How Solispec applies it
In Solispec Tmin comes from: your value in the field if you entered one; otherwise the minimum of the climatic region at the site coordinates; if no site is placed, the 1.2·UOC STC rule. The MPPT check line states which rule was used: "K_U = 1 + α·(T_min − 25)/100 = …" with the temperature and its source, or "1.2·U_oc STC (site T_min not set)".
Norms and clauses
- DSTU HD 60364-7-712:2022, Annex B.1
- DSTU-N B V.1.1-27:2010, Table 1
Related terms
- Climatic region (DSTU-N B V.1.1-27)A region of Ukraine by building climatology; for PV it gives the absolute minimum air temperature used to check string voltage.
- Maximum open-circuit voltage UOC MAXThe open-circuit voltage of a panel or string at the site minimum temperature; inverters, fuses and isolators are selected by it.
- PV stringA chain of panels connected in series: voltages add up, the current is shared; frost and the inverter MPPT window limit its length.
- MPPT and the inverter voltage windowThe inverter’s maximum power point tracker; its voltage range sets the minimum and maximum number of panels in a string.
- DSTU-N B V.1.1-27:2010: climatic regions and Tmin for PV stringsNorms explained
- DSTU HD 60364-7-712:2022: the electrics of PV systemsNorms explained
Solispec’s calculation is preliminary: for a design it has to be checked by an engineer. The values and clauses follow the current editions of the norms on the date of the page.