Maximum open-circuit voltage UOC MAX
The open-circuit voltage of a panel or string at the site minimum temperature; inverters, fuses and isolators are selected by it.
Ground frame designer
Design the ground frame for your solar plant
Solispec picks the profiles and posts, checks the frame against snow and wind to the DBN and prices it down to the last bolt.
- No sign-up
- Snow and wind check
- Drawings and estimate
Definition
The datasheet voltage UOC STC is measured at 25 °C. In winter the panel is colder and its voltage is higher. DSTU HD 60364-7-712:2022 (Annex B.1) sets how to account for it:
UOC MAX = KU · UOC STC, KU = 1 + αUoc/100 · (Tmin − 25)Here αUoc is the panel’s voltage temperature coefficient from the datasheet (%/K, negative) and Tmin is the lowest air temperature of the site. If either is unknown, the standard requires UOC MAX = 1.2·UOC STC. Clause 712.512.1.1 says that UOC MAX is taken as the rated voltage when selecting devices for a PV array.
Example for Kyiv (Tmin = −40 °C) and an illustrative panel with Uoc 49.5 V, α −0.25 %/K: KU = 1.1625, UOC MAX = 57.5 V per panel. A string of 13 such panels gives 747.5 V, below 800 V. Without α and temperature data the 1.2 rule gives 59.4 V per panel and 772.2 V for 13 panels. A fourteenth panel in the first case would give 805 V, above the 800 V limit.
UOC MAX above the inverter’s maximum input voltage is one of the few design errors that can destroy an inverter on the first frosty morning. That is why string length is always counted from the cold end, not from STC.
Where αUoc comes from: the panel datasheet gives it as the temperature coefficient of open-circuit voltage, usually in %/°C. If the maker gives it in mV/K, convert it to a percentage of Uoc. If you enter your own Uoc instead of the catalogue value and do not know α, it is more honest to use the 1.2 rule, which gives a larger margin. Everything in the DC circuit is checked against UOC MAX: the inverter input, isolators, fuses, connectors. Each device's rated voltage must be at least the string's UOC MAX. A quick check of a panel and inverter pair can be done in the string calculator.
How Solispec applies it
Solispec computes UOC MAX for each MPPT input: KU from the catalogue panel’s α and the site Tmin, or 1.2·UOC STC when α or Tmin is missing. The report shows which rule was used. The engine caps panels per string at ⌊Vmax / UOC MAX⌋ of a panel. If a string’s UOC MAX exceeds 1000 V, it asks you to check the maximum system voltage of the panels and devices against their datasheets (cl. 712.512.1.1).
Norms and clauses
- DSTU HD 60364-7-712:2022, Annex B.1; cl. 712.512.1.1
Related terms
- Site minimum temperature TminThe lowest ambient air temperature at the PV site; it sets the maximum open-circuit voltage of a string, U_OC MAX.
- Climatic region (DSTU-N B V.1.1-27)A region of Ukraine by building climatology; for PV it gives the absolute minimum air temperature used to check string voltage.
- PV stringA chain of panels connected in series: voltages add up, the current is shared; frost and the inverter MPPT window limit its length.
- MPPT and the inverter voltage windowThe inverter’s maximum power point tracker; its voltage range sets the minimum and maximum number of panels in a string.
- Maximum short-circuit current ISC MAXThe design current of a PV array, I_SC MAX = K_I·I_SC STC with K_I of at least 1.25; cables and protection are sized by it.
- DSTU HD 60364-7-712:2022: the electrics of PV systemsNorms explained
- DSTU-N B V.1.1-27:2010: climatic regions and Tmin for PV stringsNorms explained
Solispec’s calculation is preliminary: for a design it has to be checked by an engineer. The values and clauses follow the current editions of the norms on the date of the page.