Solar string sizing calculator: how many panels per string

Choose the panel, the inverter and the site's minimum temperature — the calculator shows the allowed number of panels per string and checks your choice.

Updated:

To check how many panels fit in one string of a hybrid inverter, keep the cold open-circuit voltage below the inverter maximum and the hot working voltage inside its MPPT window. For Astronergy ASTRO N5 CHSM72N-HC-590 (590 W) on Sofar HYD 10KTL-3PH at -25 °C the calculator allows 5 to 17 panels per string. Choose yours below.

How the calculator works

Open-circuit voltage rises in frost. The calculator uses U_oc max = U_oc · (1 + α · (T_min − 25) / 100), where U_oc is the datasheet value at 25 °C, α is the panel’s voltage temperature coefficient (negative, in % per kelvin) and T_min is the lowest air temperature of the site, as in HD 60364-7-712, Annex B. When T_min or α is not known, the engine falls back to 1.2 · U_oc.

Operating voltage falls in heat. Vmp at hot cells is Vmp · (1 − 0.0033 · 45), which assumes cells 45 K above 25 °C, and Vmp in frost is Vmp · (1 − 0.0033 · (T_min − 25)).

The largest string is the smaller of two numbers: the maximum input voltage of the inverter divided by U_oc max of one panel, rounded down, and the upper MPPT limit divided by Vmp in frost, rounded down, plus an allowance of two panels because exceeding the top of the MPPT window only costs some energy and does not damage the inverter. The smallest string is the lower MPPT limit divided by Vmp at hot cells, rounded up.

For a string you choose, the calculator also checks short-circuit current against the input limit (an error: the inverter will not accept it) and the operating current against the input current (a warning: the inverter clips the power). Inverters with optimizers are sized in the maker’s own configurator.

Step by step

  1. Choose the panel. Pick the model from the catalogue, so that its voltages, currents and temperature coefficient are used.
  2. Choose the inverter. Pick the inverter to load its maximum input voltage, MPPT window and input current limits.
  3. Enter the minimum temperature. Type the lowest air temperature of the site in °C. Leave it empty to use the 1.2 · U_oc rule.
  4. Read the range. The calculator shows the allowed panels per string, Voc in frost, Vmp in heat, the MPPT window and the voltage limit.
  5. Check your string. Type the number of panels you plan to use and read the checks for voltage, MPPT and current.

Assumptions and limits

  • One string on one MPPT input. If you put several strings in parallel on the same input, add their currents against the input limit and keep them the same length and orientation.
  • The panel’s maximum system voltage (usually 1000 or 1500 V) is not checked here, and neither are shading, cable losses or the DC/AC ratio. See the glossary for the DC/AC ratio.
  • Panels without a temperature coefficient in the catalogue are sized with 1.2 · U_oc whatever T_min you enter.
  • T_min is a design value of your site, not the winter average. The example uses a stated assumption; use the figure from official climate data for the real site.
  • Inverter limits come from the catalogue. Confirm them against the current datasheet before ordering.

Worked example

Example from the calculator: panel Astronergy ASTRO N5 CHSM72N-HC-590 (590 W), inverter Sofar HYD 10KTL-3PH, site minimum temperature -25 °C (an assumption for this example). One panel gives Voc 58.7 V in frost and Vmp 36.9 V with hot cells. The input accepts up to 1,000 V and tracks the maximum power point between 180 V and 960 V. The calculator gives a string of 5 to 17 panels.

A string of 17 panels reaches 999 V open-circuit in frost, below the limit of 1,000 V. A string of 18 would reach 1,057 V, and the calculator rejects it. The shortest string, 5 panels, still gives 185 V with hot cells, above the 180 V floor.

Current: one string gives Isc 14.3 A and Imp 13.6 A against input limits of 45.0 A and 32.0 A, so one string of 17 panels (10.0 kW) passes every check. Two strings in parallel on the same input would add their currents.

Reference table

Panels per string for the example panel and inverter at different minimum temperatures
T_min, °CVoc of one panel in frost, VPanels by voltage limitAllowed string, panels
-3059.4165 - 16
-2558.7175 - 17
-2058.1175 - 17
-1557.4175 - 17
-1056.8175 - 17
-556.1175 - 17

The count by voltage limit is the maximum input voltage divided by Voc in frost, rounded down. The allowed string also applies the MPPT window, as in the calculator.

What to check with an engineer

  • The T_min of the site from official climate data, and whether the standard you work under asks for another design temperature.
  • The panel’s maximum system voltage and whether the string, with the inverter, stays inside it at the coldest temperature.
  • The DC/AC ratio, the clipping you accept, and the effect of shading or different orientations on one MPPT input.
  • Cable cross-sections, DC fuses and surge protection for the strings, which this calculator does not size.
  • The current datasheets of the panel and the inverter, because catalogue data can lag behind a new revision.

How this string calculator differs from others

  • Many string calculators take a panel and an inverter and return one number. This one also shows the numbers behind it: cold open-circuit voltage, hot working voltage, the MPPT window and the input current limit.
  • It corrects the open-circuit voltage for the lowest temperature of the site with the temperature coefficient of the panel you choose, and uses a fixed safety factor when the coefficient is not known.
  • It checks the string you plan, not only the maximum, and reports voltage, MPPT and current problems separately.
  • It does not check the maximum system voltage of the panel, shading, cable losses or the DC/AC ratio. Check those with the maker or an engineer.
  • It is free, needs no sign-up, and the inputs are kept in the link.

The calculation is preliminary. A qualified engineer must check it before installation. Codes: DBN V.1.2-2:2006 (Ukraine) and the Eurocode; for other countries — snow and wind values from the national annex, entered by hand.

Frequently asked questions

Which hybrid inverter should I choose, and how do I check the strings?

Choose the inverter by the power of the plant and by what its strings allow. The calculator shows the allowed number of panels per string for the pair you pick: Sofar HYD 10KTL-3PH accepts 5 to 17 panels of 590 W in one string, up to 10.0 kW.

How many panels can I connect in series to one MPPT input?

In the example between 5 and 17. The cold open-circuit voltage (999 V at 17 panels) must stay below 1,000 V, and the hot voltage of the shortest string (185 V) must stay above 180 V.

Is there a free string calculator?

Yes. This page is free and needs no account. Choose the panel, the inverter and the lowest temperature of the site, then enter the number of panels you plan to check the string.

How many solar panels can go in one string?

As many as keep the open-circuit voltage in the coldest weather below the inverter’s maximum input voltage, and enough to keep hot-cell voltage above the MPPT floor. For Astronergy ASTRO N5 CHSM72N-HC-590 (590 W) on Sofar HYD 10KTL-3PH at -25 °C that is 5 to 17 panels. The count is the maximum input voltage divided by Voc in frost, rounded down.

How do I calculate Voc at low temperature?

Voc in frost = Voc at 25 °C · (1 + α · (T_min − 25) / 100), with α negative in % per kelvin. For the example panel, one panel gives 58.7 V at -25 °C. Multiply by the number of panels in series and compare with the inverter’s maximum input voltage, which is 1,000 V in the example.

Which minimum temperature should I use?

Use the lowest air temperature of the site from official climate data, not the winter average. A colder T_min means a higher Voc and a shorter allowed string. Leave the field empty to use the conservative 1.2 · U_oc rule, which suits a quick check but may cut the string shorter than needed.

What is the MPPT range and why must the string fit it?

The MPPT range is the voltage window in which the inverter tracks the maximum power point, here 180 V to 960 V. In heat the panel voltage falls, and below the lower limit the inverter loses power. The calculator checks the lower limit with hot cells, the upper one in frost and the input current.

What happens if the string voltage exceeds the inverter’s maximum input voltage?

The input stage can be damaged, and the warranty normally does not cover it. That is why the worst case is open circuit in the coldest weather. In the example a string of 18 panels would reach 1,057 V against the limit of 1,000 V, so the calculator rejects it.

Can strings of different length share one MPPT input?

Strings in parallel on the same input should have the same length and the same orientation and tilt, because they share one voltage. Strings of different length or direction belong on separate MPPT inputs. The calculator checks one string at a time, so add the currents yourself when you connect strings in parallel.

What if the panel current is higher than the inverter input allows?

If Isc is above the input limit the inverter will not accept the string, and the calculator marks it as an error. If the operating current is above the limit the inverter clips the power. In the example the limits are 45.0 A and 32.0 A against Isc 14.3 A and Imp 13.6 A.

Embed on your website

Free. Paste this code into your page and the calculator runs on your site, with no cookies and no data collected.

<script src="https://solispec.com/widget.js" async></script>
<solispec-calc calc="strings" lang="en"><a href="https://solispec.com/en/calculators/strings?src=embed&utm_source=embed&utm_medium=widget&utm_campaign=calc-strings">Strings and inverter — Solispec</a></solispec-calc>

Ground frame designer

Design the ground frame for your solar plant

The calculator’s values go to the designer: then the frame, the DBN checks and the estimate.