DC/AC ratio (inverter loading)

The ratio of the panels’ peak power to the inverter’s rated power; no norm sets it, it is an engineering choice.

Ground frame designer

Design the ground frame for your solar plant

Solispec picks the profiles and posts, checks the frame against snow and wind to the DBN and prices it down to the last bolt.

  • No sign-up
  • Snow and wind check
  • Drawings and estimate

Definition

DC/AC is the sum of the panels’ rated power (kWp) divided by the inverter’s rated AC power. For example, 12 kWp of panels on a 10 kW inverter gives DC/AC = 1.2.

DC/AC = ΣPпанелей / Pінвертора

Ukrainian norms do not regulate this ratio. Panels rarely produce their full rated power: sun angle, heat and soiling get in the way. So moderate inverter loading usually pays off — the inverter runs near its rating for longer and only infrequent peak hours are lost. The price is clipping of peaks on clear, cool days.

DC/AC does not replace the electrical checks. Even with a sensible ratio a string can exceed the input voltage in frost (UOC MAX), and parallel strings can exceed the input current (ISC MAX). For the grid connection a different number matters: the allowed power under the contract, which is compared with inverter power, not panel power.

How to choose the ratio in practice. A south-facing array at the optimum tilt has the highest peaks, so inverter loading leads to clipping sooner. An east-west or low-tilt array has lower, broader peaks, so a higher DC/AC loses less energy. The annual yield and payback for a chosen size can be estimated in the PV payback calculator, and the electrical input limits are checked by the string calculator. Choose the final inverter power with the allowed connection power in mind: it is often the hard limit.

How Solispec applies it

The Solispec engine computes DC/AC for each inverter and flags the extremes. These thresholds are the app’s rules, not norm requirements: above 1.3 — "will clip peaks" (warning), above 1.5 — "heavily overloaded" (error), below 0.7 — "inverter too large". Between 0.7 and 1.3 it raises nothing.

String calculator

Related terms

The whole glossary

Solispec’s calculation is preliminary: for a design it has to be checked by an engineer. The values and clauses follow the current editions of the norms on the date of the page.