How to size an inverter and battery for a home: 4 steps with numbers
How to choose an inverter and battery for a home: peak power with motor starts, phases, 48 V, battery capacity for backup hours. A worked example.
An inverter is sized by the peak power of everything that runs at the same time, including the starting surge of motors. A battery is sized by the energy it has to deliver during the hours without power. The formula is simple: capacity = load × hours / (depth of discharge × inverter efficiency). Below are four steps with numbers for a typical house, from a list of appliances to a concrete inverter rating and number of batteries.
Step 1. The load list: power and energy
Start with a sheet of paper, not a catalogue. Write down everything that has to run from the inverter and two numbers for each appliance: its power (W) and how many hours a day it runs. The power is on the appliance's rating plate or in its manual.
Typical values used by our backup time calculator:
- fridge — about 150 W;
- boiler circulation pump — about 100 W;
- router — about 20 W;
- LED lighting — about 50 W;
- TV — about 100 W;
- laptop — about 60 W.
Appliances with a heating element (washing machine, kettle, water heater, iron) draw many times more. Take them from the rating plate, never by eye.
Peak power and starting currents
The inverter has to withstand the worst instantaneous load, not the average one. It is counted as the sum of everything that may run at once, plus the starting surges of motors.
A fridge compressor, a circulation pump, a well pump or an air conditioner draws several times its running current at start-up. That lasts a fraction of a second to a few seconds, but an inverter with no margin shuts down on overload exactly at that moment. The exact starting current comes from the appliance maker or from a clamp meter. Without it, assume a generous multiple in a preliminary estimate, and for a well pump always look it up in the datasheet.
Energy per day
The second number is energy, kWh per day: power × hours of use, added up over all appliances. A fridge runs in cycles, so for it take the annual consumption from the energy label and divide by 365. Daily energy is needed to estimate the battery capacity and, if panels are planned, the size of the plant.
Step 2. Single phase or three phase
Look at the contract with the distribution system operator (DSO): it states the number of phases and the allowed connection capacity. That decides the class of inverter.
- Single-phase connection — a single-phase inverter only. A three-phase inverter cannot be connected to a single-phase supply.
- Three-phase connection — either a three-phase inverter for the whole house or a single-phase one for a separate group of backed-up circuits on one phase.
In Ukraine, the total rated power of a PV plant's inverters may not exceed the allowed capacity in the contract (Distribution System Code, cl. 4.1.35 and 4.12.1). It is the inverters' power that is compared, not the panels'.
Unbalanced load
In a three-phase house most appliances are single-phase, and they are spread over the phases unevenly. The fridge and boiler may sit on phase A, the washing machine and kitchen on phase B. So for a three-phase inverter, count the load on each phase separately and check against the datasheet:
- the maximum power the inverter delivers on one phase (for many models it is only a share of the total);
- whether the output supports an unbalanced load.
If the peak load on one phase exceeds what that phase allows, the inverter shuts down even though the total power is not used up.
Step 3. Inverter power and surge rating
An inverter datasheet has two different numbers:
- rated (continuous) power — what it delivers for hours; it must be no less than the sum of loads running together, with a margin;
- peak power — a short overload for a few seconds; it must cover the starting surges from step 1.
Look not only at the peak value but also at how long the inverter holds it. A margin on continuous power is needed because loads grow over the years: another heater, an air conditioner, a car charger. In our catalogue, single-phase hybrid inverters range from 3.6 to 11 kW and three-phase ones from 6.5 kW upwards; compare models in the inverters section.
The type matters too. A grid-tied inverter works only while the grid is up, and batteries do not connect to it. Backup needs a hybrid: it powers the house from the batteries during an outage and charges them from the panels. How grid-tied, hybrid and off-grid inverters differ is covered in which inverter type to choose.
Step 4. Battery voltage and capacity
Why 48 V rather than 12 or 24
The current on the battery side is power divided by voltage. For a 3 kW load:
- 12 V — 250 A;
- 24 V — 125 A;
- 48 V — 62.5 A.
Twice the current means thicker cables, larger fuses and four times the losses in the same cable. So 12 and 24 V systems make sense for small off-grid loads, while 48 V is the standard for a home. In our catalogue, low-voltage (LV) batteries are mostly 48–51.2 V modules, and single-phase hybrids take a battery input of roughly 40–60 V. Three-phase models often work with high-voltage (HV) stacks of several hundred volts. The battery's LV or HV class must match the inverter's input, and the battery maker must confirm compatibility with the inverter.
Capacity from backup hours
The formula is the same as in the backup time calculator:
Usable energy = count × capacity × DoD × efficiency
Hours = usable energy / load power
DoD is the allowed depth of discharge from the battery datasheet (80 to 100 % in our catalogue, most often 90 %). Inverter efficiency is taken as 0.9. The calculation assumes no charging from the panels — night or an overcast day. From this, the nominal capacity needed is:
Capacity = load × hours / (DoD × 0.9)
Module capacities are listed in the batteries section. Amp-hours, LiFePO4 and AGM are covered in inverter battery capacity.
If there will be solar panels
Then you need a hybrid inverter with a PV input, and its datasheet adds three important parameters:
- MPPT range — the voltage window in which the inverter keeps a string at its maximum power point (more in what MPPT is); for single-phase hybrids in the catalogue the upper limit is between 245 and 560 V;
- maximum input voltage — a hard limit the string must never exceed, even on a frosty morning;
- maximum PV input power — often higher than the AC output rating.
PV input and AC output are different things. A 5 kW inverter delivers at most 5 kW to the house, even with 6 kW of panels on it. The ratio of panel power to inverter power is the DC/AC ratio. The Solispec engine warns above 1.3 and flags an error above 1.5.
Check the number of panels per string in the string calculator, and why a string has to be sized for the coldest morning in the article how many panels per string. The plant size for your yearly consumption comes from the system size calculator.
Example: sizing a typical house
A house with a single-phase connection. Appliances: fridge, boiler pump, router, LED lighting, TV and washing machine. For the washing machine take 2000 W while it heats water (check your own rating plate).
1. Peak power. Running together: 150 + 100 + 20 + 50 + 100 = 420 W; with the washing machine, 2420 W. For the start of the compressor and the pump take three times their power for a few seconds: +300 W and +200 W. The worst moment is about 2.9 kW.
2. Inverter. Continuous power at least 2.4 kW, peak at least 2.9 kW. A 3.6 kW inverter passes on paper, but a second heating appliance of 1.5–2 kW (kettle, microwave) together with the washing machine will overload it. A 5 kW inverter leaves room for that and has a larger PV input for panels. We would choose a single-phase 5 kW hybrid with a 48 V battery.
3. Energy per day. Router 20 W × 24 h = 0.48 kWh; lighting 50 W × 5 h = 0.25; TV 100 W × 4 h = 0.4; boiler pump in the heating season 100 W × 24 h = 2.4; fridge, with the compressor running a third of the time, 1.2; washing machine, one cycle, take 1 kWh (the label is more precise). In total about 5.7 kWh a day, or roughly 2100 kWh a year if every day is like that.
4. Battery. During an outage the washing machine stays off, so the load is 420 W. Backup for the night is 8 hours: 420 × 8 = 3.36 kWh at the inverter output. Capacity needed: 3.36 / (0.9 × 0.9) ≈ 4.15 kWh.
One 5.12 kWh module at 51.2 V with 90 % DoD gives 5.12 × 0.9 × 0.9 ≈ 4.15 kWh of usable energy, about 9.9 hours at 420 W. For long outages, two modules give about 8.3 kWh and 19.7 hours. The estimate is conservative: the fridge is counted at full power all the time, so the real margin will be a little larger.
Common mistakes
- Sizing by average power. An inverter trips on the peak, not on the average.
- Forgetting starting currents. Especially a well pump: it is the one that most often trips the inverter.
- Buying a three-phase inverter for a single-phase connection, or exceeding the allowed capacity in the contract.
- Not counting the load per phase. The total may fit while one phase does not.
- Taking the battery's full capacity. Without DoD and efficiency the backup hours are overstated.
- Confusing PV input with inverter power. 8 kW at the input does not mean 8 kW at the sockets.
- Not checking battery–inverter compatibility: LV/HV class, voltage and the maker's list.
Checklist before you buy
- Number of phases and allowed capacity from the DSO contract.
- Appliance list: power, hours of use, starting currents.
- Peak power and the load on each phase.
- Inverter: continuous power with a margin, peak power with its duration, type (hybrid for backup).
- Battery: 48 V (LV) or HV to match the inverter input, DoD from the datasheet, compatibility.
- Capacity from the formula for the hours you need.
- With panels — MPPT range, maximum voltage, PV input, DC/AC ratio.
Cable sizes, protective devices and earthing are set by the design; in Ukraine per ПУЕ:2026 and ДБН В.2.5-23:2025.
Frequently asked questions
Which inverter is best for a home?
The one that passes all four steps: continuous and peak power with a margin over your appliance list, the right number of phases, a 48 V or HV battery input matching the chosen battery and, if needed, a PV input for your panels. The brand comes second: the datasheet figures and compatibility are what matter.
How do I choose an inverter for a flat?
The same way, but it is usually simpler: the connection is single-phase and the load is a router, lights, a fridge and a laptop. A compact single-phase inverter is often enough. Think separately about where to place the battery, following its maker's requirements for the room.
How many hours will a battery last?
Usable energy (capacity × DoD × 0.9) divided by the load power. A 5.12 kWh module at 420 W lasts about 9.9 hours. Put your own numbers into the backup time calculator.
Can I add panels later?
Yes, if you buy a hybrid inverter with a PV input from the start. Panels can then be added without replacing the inverter. A grid-tied inverter does not support batteries, so it gives no backup.
Should the inverter be larger than the panels?
Not necessarily. Panels are often installed with a little more power than the inverter. What matters is that the DC/AC ratio stays within reasonable limits and the strings pass the input voltage and current checks.
A preliminary estimate. A qualified engineer must check it before installation.