How long a battery lasts in a blackout: a flat and a bakery
How many hours a battery lasts in a power cut. A 400 W flat with a 6 kW hybrid inverter for 15 and 24 hours, a small bakery with 15 kW of critical load for 5–7 hours, discharge current and a cold battery.
One 5.12 kWh battery module runs a flat with a 400 W load for 10.4 hours, not the naive 12.8. Fifteen hours need two modules (20.7 h), a full day needs three (31.1 h). A bakery with 15 kW of critical load for 6 hours needs 11 modules of 10.24 kWh (6.1 h). The calculation is preliminary.
Both cases come from a group of hybrid inverter installers in Ukraine: a flat with a 6 kW hybrid and 15–24 hour outages ("is one 5 kWh battery enough?"), and a bakery whose equipment totals 30–40 kW, with 15 kW of it critical for 5–7 hours. Below: the hand calculation, the same numbers from the how long the batteries last calculator, and what the calculator does not count: discharge current, motor starts and cold.
How to count the hours of backup
- Capacity. The module rating in kWh times the number of modules.
- Depth of discharge (DoD). The share of capacity you may use. 90 % per the datasheet in both examples.
- Inverter efficiency. Part of the energy turns into heat. The calculator takes 0.9.
- Hours = capacity × DoD × efficiency ÷ load power.
DoD 0.9 × efficiency 0.9 = 0.81: each kWh of rating gives the load 0.81 kWh. The calculator assumes the outage starts with a fully charged battery and that the panels do not charge meanwhile (night or an overcast day).
The flat: 400 W for 15 and 24 hours
A fridge, router, lights, a laptop and a TV average about 400 W. A 6 kW hybrid inverter, LV 51.2 V modules of 5.12 kWh with 90 % DoD and 100 A continuous current.
By hand: 400 W × 15 h = 6.0 kWh, ÷ 0.81 = 7.4 kWh of rating. For a full day 400 W × 24 h = 9.6 kWh, ÷ 0.81 = 11.9 kWh.
| Modules | Capacity, kWh | Usable energy, kWh | Hours at 400 W |
|---|---|---|---|
| 1 | 5.12 | 4.15 | 10.4 |
| 2 | 10.24 | 8.29 | 20.7 |
| 3 | 15.36 | 12.44 | 31.1 |
One module does not reach even 15 hours. Two cover 15 hours with margin, a full day needs three (about 16 kWh). The 6 kW inverter carries 400 W in all three cases.
The usual mistake: 5.12 ÷ 0.4 = 12.8 h. That is what you get when you forget the DoD and the inverter losses. The real 10.4 hours are 2.4 hours fewer.
There is also a current limit. One module delivers 100 A × 51.2 V ≈ 5.1 kW continuously, less than the 6 kW of the hybrid. If a kettle, a water heater or a washing machine starts while the fridge runs, one module limits the power before it runs out of energy. Two modules in parallel give about 10.2 kW.
The bakery: 15 kW of critical load for 5–7 hours
The bakery's equipment totals 30–40 kW. Only the critical part stays on the inverter: ovens, the dough mixer, the cold rooms, 15 kW together. The rest stops during an outage. The critical loads go on a separate line from the inverter's backup output. A qualified electrician designs and installs that line, its protection and cables to the local electrical rules (in Ukraine, PUE:2026).
A 15 kW three-phase hybrid inverter, LV 51.2 V modules of 10.24 kWh with 90 % DoD and 100 A continuous current.
By hand: 15 kW × 6 h = 90 kWh, ÷ 0.81 = 111.1 kWh of rating, that is 11 modules. For 5 hours 75 ÷ 0.81 = 92.6 kWh (10 modules), for 7 hours 105 ÷ 0.81 = 129.6 kWh (13 modules).
| Modules | Capacity, kWh | Usable energy, kWh | Hours at 15 kW |
|---|---|---|---|
| 10 | 102.4 | 82.94 | 5.5 |
| 11 | 112.64 | 91.24 | 6.1 |
| 12 | 122.88 | 99.53 | 6.6 |
| 13 | 133.12 | 107.83 | 7.2 |
Does the inverter carry it
A 15 kW inverter carries 15 kW with nothing to spare. At 16 kW the calculator already flags an overload: the inverter shuts down and there are no backup hours at all. The dough mixer's motor and the cold rooms' compressors draw several times their rated current when they start. The calculator does not count starting currents. Check them against the equipment datasheets and the inverter's peak power, and stagger the starts of large motors.
Discharge current
15 kW from a 51.2 V battery is 15000 ÷ 51.2 = 293 A before losses. A module delivers up to 100 A continuously, so at least 3 modules must work in parallel. Eleven modules leave margin. A high-voltage (HV) battery draws less current and needs thinner cables for the same power, but works only with a compatible inverter. Check compatibility and settings in the documentation of your model.
In winter: a cold battery
In winter the group's most common question is why the battery will not take full charging current. The BMS of a lithium iron phosphate battery limits charging current in the cold. Posts in the group name a limit of about +15 °C and a charging stop at about 0 °C. The exact limits differ between models; the battery datasheet gives them.
- The calculator assumes the outage starts with a full battery. If there are only a few hours between outages, a cold battery may not recharge in time, and the next outage starts with less charge.
- The available capacity is also lower in frost. The calculator does not account for cold, so leave a margin.
- The simplest fix: keep the battery in a heated room, within the temperature range of its datasheet.
Check the charging current and temperature limits in the inverter settings in the documentation of your model.
Switch the inverter off at 10 %?
The longest thread in the group was whether to switch the inverter off by hand when the charge drops to 10 %. The calculator's hours already run down to the 90 % DoD limit, that is to about 10 % left. A hybrid inverter usually disconnects the load by itself at a set low state of charge and recharges the battery when the grid or the sun returns. Which threshold is set and how the system recovers from a deep discharge: check in the documentation of your inverter and battery model.
A higher threshold cuts the hours in proportion. Stopping at 20 % instead of 10 % gives the flat's two modules 20.7 × 80 ÷ 90 = 18.4 h instead of 20.7.
Checklist before choosing a battery
- List what must run without the grid and its average power. For a fridge take the average, not the rating.
- Set the hours: the longest outage worth riding through.
- Count the hours for 1, 2 and 3 modules in the how long the batteries last calculator.
- Check that the inverter carries the load including motor starts.
- Check the discharge current: power ÷ battery voltage against the modules' continuous current.
- Think about winter: where the battery stands and whether it recharges between outages.
- Compare module specifications in the battery catalogue; the formula with chemistries and frost is in the article on battery capacity.
Hourly energy balance with panels and battery, battery and inverter compatibility, cables and protection, the bill of materials and the client proposal come from the Solispec configurator.
The calculation is preliminary. The loads in the examples are indicative; the calculator takes an inverter efficiency of 0.9. A qualified engineer must check the calculation before installation, and only a qualified electrician installs the system.
FAQ
Is one 5 kWh battery enough for 15 hours?
Not for a 400 W load. A 5.12 kWh module with 90 % DoD and 0.9 inverter efficiency gives 4.15 kWh, that is 10.4 hours. Fifteen hours need two modules (20.7 h).
How many batteries does a bakery need for 15 kW over 6 hours?
About 111 kWh of rating: 11 modules of 10.24 kWh give 6.1 hours. A 15 kW inverter carries that load with nothing to spare for motor starts.
Why does a battery charge more slowly in winter?
The BMS limits charging current in the cold. The group names a limit of about +15 °C and a stop at about 0 °C; the exact values are in the battery datasheet.