Inverter battery capacity: how to size it, and LiFePO4 or AGM

How to size a battery for an inverter: the formula with DoD and efficiency, LiFePO4 vs AGM and gel, frost, discharge current, examples for 800 W and 10 kWh.

By Solispec editorial10 min read

Battery capacity is sized in kilowatt-hours of energy you can actually take out, not in amp-hours: energy needed ÷ (DoD × inverter efficiency × temperature factor). For 4 hours of an 800 W load that is about 4 kWh of nominal LiFePO4 capacity, i.e. one 51.2 V 100 Ah module. A lead-acid AGM or gel bank needs roughly twice the nominal capacity for the same job, because it is only discharged halfway.

Below: the formula, the differences between chemistries, the effect of frost, discharge current, worked examples and common mistakes.

Amp-hours and kilowatt-hours

The battery label says Ah, but the inverter and your appliances use energy, i.e. Wh. The conversion is simple:

energy, kWh = voltage, V × capacity, Ah ÷ 1000

  • a 51.2 V × 100 Ah module = 5.12 kWh;
  • a 12 V × 200 Ah lead-acid battery = 2.4 kWh;
  • 100 Ah at 12 V and 100 Ah at 48 V are different amounts of energy — by a factor of four.

So compare batteries in kWh only. Amp-hours without the voltage tell you nothing.

The sizing formula

  1. Energy needed. Add up the power of everything running at the same time and multiply by the hours. Fridge ≈ 150 W, router ≈ 20 W, LED lighting ≈ 50 W, boiler pump ≈ 100 W. A fridge cycles on and off, so its average power is lower than the rated one.
  2. Depth of discharge (DoD). The share of capacity you are allowed to use. Take it from the battery datasheet.
  3. Inverter efficiency. Part of the energy turns into heat during conversion. Our backup calculator assumes 0.9.
  4. Temperature factor. In a warm room it is 1. In a cold one the available capacity is lower; the datasheet gives the exact curve.

Nominal capacity = energy needed ÷ (DoD × efficiency × temperature factor)

The calculator works the other way round — how long a given battery lasts: usable energy = count × capacity × DoD × 0.9, and hours = usable energy ÷ load power. It ignores charging from the panels (night or a cloudy day) and the cold too: if the battery sits in an unheated room, add the margin yourself.

LiFePO4, AGM or gel

The main difference is not the nominal capacity but how much of it you can take, and how many times.

  • LiFePO4 (LFP). In our battery catalogue the datasheet DoD ranges from 80 to 100 %, most often 90–95 %. Datasheet cycle life ranges from 2,500 to 8,000 cycles under the conditions the manufacturer states. The voltage barely sags under load until the end of discharge. A BMS is built in.
  • AGM. Sealed lead-acid. To reach its rated life it is usually discharged no deeper than 50 %. Datasheet cycle life is in the hundreds and drops quickly with depth of discharge. At high current it delivers less than the label says (the rated capacity is for a slow discharge, usually 10 or 20 hours).
  • Gel. Also lead-acid; it tolerates deep and cyclic discharge better than AGM, but with the same limits: a practical DoD of about 50 %, datasheet cycle life in the hundreds, rarely above a thousand.
ChemistryDoD for daily cyclingRound-trip efficiencyDatasheet cycle lifeCharging below freezing
LiFePO4 (LFP)80–100 %, most often 90–95 %≈ 90–96 %2,500–8,000 cycles (Solispec catalogue)usually not allowed below 0 °C without a heater
AGM≈ 50 %≈ 75–85 %hundreds of cycles, ≈ 300–800 at 50 % DoDpossible at reduced current with temperature-compensated voltage
Gel (GEL)≈ 50 %≈ 75–85 %≈ 500–1,200 at 50 % DoDpossible at reduced current with temperature-compensated voltage

Round-trip efficiency is the share of the charged energy the battery gives back. It decides how much solar energy goes into charging; the capacity formula above accounts for the inverter's efficiency on discharge. The ranges in the table are typical of datasheets; for your battery take the figures from its own datasheet.

Comparing prices "per box" is wrong. Work out the cost per cycle:

price ÷ (cycles × nominal kWh × DoD)

That gives the price of one kilowatt-hour the battery delivers over its life. For a system that cycles every day, LiFePO4 usually wins by this method even when it costs more up front. For a backup used a few times a year the gap is smaller, and the ageing of lead-acid on float becomes the main issue.

Frost: where to put the battery

Most LiFePO4 datasheets forbid charging below 0 °C, and many limit the charge current already in a band of roughly 0 to +5…+10 °C. The BMS then simply refuses the charge. Discharging in the cold is allowed, but less capacity is available.

In a Ukrainian winter this is a practical problem. An unheated garage or shed freezes below zero. In the morning the panels are already producing, but the battery will not charge until it warms up. So:

  • put the battery in a heated room that stays above +5 °C through the winter;
  • if that is not possible, choose a model with built-in heating (the datasheet says so) and include a temperature factor in the sizing;
  • keep the battery out of the sun and away from the boiler — heat shortens the life of any chemistry;
  • lead-acid batteries lose capacity in the cold too, and their room must be ventilated.

Discharge current and inverter power

Capacity answers "how long", current answers "can it deliver". A 5 kW inverter on 48 V at full load draws from the battery about:

5000 W ÷ (48 V × 0.9) ≈ 116 A

In the catalogue the continuous current of low-voltage modules ranges from 25 to 230 A, typically 100 A. One 100 A module will not give a 5 kW inverter its full power, even if its capacity is enough. Two modules in parallel share the current. For a 10 kW inverter the current is about 230 A — three 100 A modules, or modules rated for more. Check the maximum charge and discharge current in the inverter datasheet as well.

48 V, parallel modules and BMS communication with the inverter

Low-voltage (LV) systems run at 48 or 51.2 V. Capacity grows by adding modules in parallel. The manufacturer limits how many can be combined: in the catalogue, from a few to a few dozen. Do not mix models and, where possible, batches with different wear.

High-voltage (HV) systems are stacks of modules in series, from about 100 to 800 V. They only work with HV inverters whose battery voltage range matches the stack. In the inverter catalogue each hybrid shows whether it needs an LV or HV battery and its voltage range.

BMS communication with the inverter runs over CAN or RS485. Through it the inverter knows the state of charge, the current limits and the temperature, and lowers the charge in the cold by itself. Without it the inverter works by voltage alone, which is worse for LiFePO4. Before buying, make sure the inverter supports this battery's protocol: each battery card in the catalogue lists compatible inverters.

Example 1: 4 hours of backup for 800 W

An average load of 800 W during a 4-hour outage.

  • Energy needed: 0.8 kW × 4 h = 3.2 kWh.
  • LiFePO4, DoD 90 %, efficiency 0.9, warm room: 3.2 ÷ (0.9 × 0.9) ≈ 3.95 kWh nominal. One 5.12 kWh module gives 5.12 × 0.9 × 0.9 ≈ 4.15 kWh, i.e. ≈ 5.2 hours at 800 W.
  • The same module in a garage with a factor of 0.8 (our assumption for the example): ≈ 3.3 kWh, ≈ 4.1 hours — just about enough.
  • AGM, DoD 50 %: 3.2 ÷ (0.5 × 0.9) ≈ 7.1 kWh. On 48 V that is four 12 V batteries of about 150 Ah in series — before the losses at high current.

The inverter must carry 800 W with headroom for the starting currents of a pump or fridge.

Example 2: 10 kWh a day with panels

A house uses 10 kWh a day; the panels cover part of it in daytime, and the battery has to cover the evening and night. Let us assume 6 kWh is used in the evening and at night (your split may differ — an hourly profile gives it).

  • Nominal: 6 ÷ (0.9 × 0.9) ≈ 7.4 kWh — two 5.12 kWh modules (10.24 kWh, ≈ 8.3 usable).
  • During the day the panels must cover both the daytime load and the battery charge, with losses. In a Ukrainian winter generation is much lower, and the battery will not reach full charge every day.

The system size calculator sizes the plant and the number of batteries for your yearly consumption and outage hours — hour by hour, with PVGIS data for your address.

How long a battery lasts

Hours = nominal × DoD × 0.9 ÷ load power, kW

  • 5.12 kWh LiFePO4 (DoD 90 %) at 500 W — ≈ 8.3 h; at 1000 W — ≈ 4.1 h.
  • 10.24 kWh at 1000 W — ≈ 8.3 h; at 2000 W — ≈ 4.1 h.
What runs during the outagePowerHoursEnergy neededLiFePO4 nominal (DoD 90 %, efficiency 0.9)
router and LED lighting70 W80.56 kWh≈ 0.7 kWh
+ fridge (≈ 60 W on average over its cycles)130 W121.56 kWh≈ 1.9 kWh
+ boiler pump230 W122.76 kWh≈ 3.4 kWh
average load from example 1800 W43.2 kWh≈ 4.0 kWh
evening and night from example 2——6 kWh≈ 7.4 kWh

Nominal in the table = energy needed ÷ (0.9 × 0.9), a warm room, no recharging from the panels. The first three rows are covered by one 5.12 kWh module.

Enter your battery from the catalogue, the count, the inverter and the load in the backup calculator. It also warns you if the inverter cannot carry the load.

Common mistakes

  • Comparing Ah without the voltage.
  • Counting the full nominal capacity and forgetting DoD and efficiency.
  • Buying lead-acid and draining it to zero every day — its life is gone in a season.
  • Putting LiFePO4 in an unheated garage without heating.
  • Sizing the capacity but not checking the current: one 100 A module under an 8–10 kW inverter.
  • Buying a battery whose BMS protocol the inverter does not support.
  • Adding a new module to old ones of a different model.

Sources

  • IEC 62619:2022 — safety requirements for secondary lithium cells and batteries for industrial applications, including stationary energy storage.
  • IEC 62109-1:2010 and IEC 62109-2:2011 — safety of power converters for use in photovoltaic power systems; part 2 covers inverters.
  • IEC 61427-1:2013 — secondary cells and batteries for renewable energy storage; part 1 covers photovoltaic off-grid applications, requirements and test methods.
  • IEC 60896-21:2004 and IEC 60896-22:2004 — stationary valve-regulated lead-acid batteries (VRLA, which include AGM and gel): test methods and requirements.
  • UN 38.3 — tests for lithium batteries before transport (UN Recommendations on the Transport of Dangerous Goods, Manual of Tests and Criteria).
  • Manufacturers' datasheets of the LiFePO4 modules in the battery catalogue: DoD, cycle life and the conditions it is measured under, charging temperature limits, continuous and peak current.
  • Hybrid inverter datasheets: battery voltage range, maximum charge and discharge currents, supported BMS protocols.

FAQ

What battery does a 5 kW inverter need?

For a 5 kW LV hybrid — a 48/51.2 V LiFePO4 bank whose continuous current covers ≈ 116 A at full power: usually two 100 A modules or one rated for more. Size the capacity for your hours and load with the formula above.

And a 10 kW inverter?

The full-power current is about 230 A at 48 V, so three or more modules, or an HV stack if the inverter is high-voltage. Again, size the capacity from energy, not from the inverter's power.

LiFePO4 or gel — which is better for a solar system?

For daily cycling, LiFePO4: higher DoD, several times the datasheet cycle life, lower cost per cycle. Gel makes sense where discharges are rare and the upfront budget is tight.

Can LiFePO4 be charged in frost?

Most datasheets forbid charging below 0 °C. Keep the battery warm or choose a model with heating.

Can an old and a new module be combined?

Only if the manufacturer allows it for that model. Different models and chemistries are not combined in one bank.

This is a preliminary calculation. A qualified engineer must check the system before installation.

YieldElectrics

News and design tips

What’s new in Solispec, changes to the standards and practical tips on designing solar power systems.

What interests you

How we handle your data: privacy policy.

Ground frame designer

Design the ground frame for your solar plant

Solispec picks the profiles and posts, checks the frame against snow and wind to the DBN and prices it down to the last bolt.

  • No sign-up
  • Snow and wind check
  • Drawings and estimate