Norms · DIN EN 1991-1-3/NA · DIN EN 1991-1-4/NA

Snow and wind loads on a hall roof with PV: DIN EN 1991 NA

The snow load on a hall roof with PV follows from s = μ1 · C_e · C_t · s_k to DIN EN 1991-1-3/NA; for roof pitches up to 30° μ1 = 0.8. For Halle (Saale) (snow zone 2, s_k = 0.85 kN/m²) that gives 0.68 kN/m² on the roof and 1.02 kN/m² as the design value. The wind load grows with height: the peak velocity pressure q_p in Halle (Saale) is 0.64 kN/m² at 3 m and 0.92 kN/m² at 10 m (terrain category II). This page works both through for an example hall.

Updated:

Halle (Saale) or a hall roof?

Someone searching “Schneelast Halle” means either the city of Halle (Saale) or the roof of a hall. The city lies at 114 m above sea level in snow zone 2 and wind zone 2: s_k = 0.85 kN/m², q_b = 0.39 kN/m². The same method applies to every hall at every site; only the zone and the altitude change.

Snow load on the hall roof

The snow load on the roof is s = μ1 · C_e · C_t · s_k. The shape coefficient is μ1 = 0.8 for pitches up to 30°, then falling linearly to 0 at 60°; C_e = 1.0 for normal topography and C_t = 1.0 with no reduction for heat loss. The design value follows with γ_Q = 1.5. On a lightweight hall with a low roof dead weight, snow often governs the capacity reserve, and the PV system (Solispec takes the modules at 12 kg/m², plus rails and fixings) uses part of it.

The table gives the snow load on the roof for the snow zones up to 200 m above sea level:

Zones_k, kN/m²roof 0.8 · s_k, kN/m²design 1.5 · 0.8 · s_k, kN/m²
10.650.520.78
1a0.810.650.97
20.850.681.02
2a1.060.851.27
31.100.881.32
3a1.381.101.66

Special cases for snow: drifts and the northern lowlands

  • Drifts at parapets, rooftop structures and behind tall module rows are applied to Annex B of EN 1991-1-3 (B.2: μ2 = γ · h / s_k with γ = 2 kN/m³, between 0.8 and 2.0); the standard has no separate rule for the rows themselves, the structural engineer decides. The Solispec calculator works out the uniform load μ1 · s_k, drifts are added separately
  • In the districts the DIBt marks in the northern German lowlands (zones 1 and 2, for example Hamburg and Berlin) an accidental design situation with 2.3 · s_k must also be checked
  • Bavaria also has zones 3a and above 3a, and high ground above 800 m has values of its own

Wind load: why height matters

The peak velocity pressure is q_p(z) = c_e(z) · q_b and rises with the height z above ground. For Halle (Saale) the calculation gives, for terrain category II (inland, open country) and III (suburb, buildings):

Height z, mc_e (II)q_p (II), kN/m²c_e (III)q_p (III), kN/m²
31.640.641.280.50
62.040.791.390.54
102.350.921.710.67

Wind load at great height and on the flat roof

At great altitude above sea level q_b stays unchanged up to 800 m under the national annex; from 800 to 1100 m a factor (0.2 + H/1000) is added, and above that special consideration is needed. At great height above ground c_e grows, as the table shows.

On a flat roof (pitch up to 5°, sharp eaves) DIN EN 1991-1-4 Table 7.2 sets the areas F, G, H and I. Their size follows from e = min(b; 2h). For a hall with b = 30 m and h = 10 m, e = 20 m, and with q_p = 0.92 kN/m² at 10 m height (category II) the external pressures without modules are:

Areac_pe,10w_e, kN/m²
F-1.8-1.65
G-1.2-1.10
H-0.7-0.64
I±0.2±0.18

What this means for modules and ballast

  • Tilted modules have coefficients of their own; Solispec uses the values of EN 1991-1-4 Table 7.6 (free-standing monopitch canopy) with an edge factor k_z of 1 in the middle, 1.5 at the edge and 2 at the corner
  • Ballast is sized for wind (uplift and sliding); snow must not count as ballast
  • The hall roof must carry ballast, modules and snow together, including the local drift behind the rows; the hall’s structural engineer checks this
  • When combining actions Solispec takes ψ0 = 0.5 for snow (up to 1000 m above sea level) and 0.6 for wind

Checklist for the design

  • Municipality and altitude above sea level noted, snow zone and wind zone from the DIBt lists
  • s_k from the zone formula or table, cross-checked with the page “Zones in Germany”
  • Roof pitch checked: up to 30° μ1 = 0.8
  • Drift at parapets, rooftop structures and tall module rows applied to Annex B or excluded with a reason
  • Terrain category, building height and areas F to I set, coefficients for the modules chosen
  • Capacity reserve of the roof shown for modules, ballast and snow with drift (especially on lightweight halls)
  • Structural design checked by an engineer

Frequently asked questions

How big is the snow load on a hall roof?

To DIN EN 1991-1-3/NA s = μ1 · C_e · C_t · s_k; up to 30° pitch μ1 = 0.8. In Halle (Saale) with s_k = 0.85 kN/m² that is 0.68 kN/m², design value 1.02 kN/m².

How big is the snow load in Halle (Saale)?

Halle (Saale) is in snow zone 2; the ground snow load is s_k = 0.85 kN/m² at 114 m above sea level.

What wind loads must a building take at great height?

The peak velocity pressure grows with height: in Halle (Saale) from 0.64 kN/m² at 3 m to 0.92 kN/m² at 10 m (category II). Above 800 m above sea level a factor on q_b is added.

What is special about a lightweight hall with PV?

The roof has little dead weight and often little capacity reserve. Modules, ballast and snow with drift have to be shown together, and the wind can lift the roof.

Is this page enough for a structural design?

No. It shows the method and guide values. A structural engineer does the check for your building to the country’s standards.

Sources: the standards

  • DIN EN 1991-1-3/NA:2010-12, Nationaler Anhang, Schneelasten (Zonen: Fassung 2019-04); DIN EN 1991-1-3 (5.2, Anhang B)
  • DIN EN 1991-1-4/NA:2010-12, Nationaler Anhang, Windlasten; DIN EN 1991-1-4 (7.2.3, Tabelle 7.2)
  • DIN EN 1990/NA, Grundlagen der Tragwerksplanung

The values are guide values. Drift, the coefficients of the modules and the capacity reserve of the roof are for a structural engineer to check for the actual building.