Solar ballast calculator for a flat roof
Choose the place (roof or ground), the roof zone, the number of panels, the tilt and the supports — the calculator shows how much ballast stops uplift and sliding and whether the chosen blocks are enough.
Updated:
Codes: DBN V.1.2-2:2006 (Ukraine) · EN 1991-1-3 / EN 1991-1-4 with national annex (PL, DE, ES) · EN 1990 · EN 1993-1-3
Solispec computes flat-roof ballast against wind uplift and against sliding for any panel and any ballast block. It is not tied to one maker’s mounting system: the wind force, the surface friction and the weights decide. For one row of 5 panels at 15 degrees in Kyiv, 6 m up, the calculator gives 1,879 kg in the middle zone.
How the calculator works
The calculator turns the characteristic wind load of the site into a force on one row of panels and compares it with the weight that holds the row down. Wind pressure at the height of the array is Wm = γ · W0 · ce(z) · Calt, where W0 is the characteristic wind pressure, ce(z) the EN 1991-1-4 4.5 exposure factor for height and terrain (categories I to IV; the uplift coefficient from EN 1991-1-4 is defined on the peak pressure, so ce replaces Ch of Table 9.01 and W0 is taken as the basic pressure qb), Calt the altitude factor and γ the partial factor for the return period, as in DBN V.1.2-2:2006. Pages for Poland, Germany and Spain use the same chain with EN 1990 and EN 1991-1-4: the national annex value q_b, a partial factor of 1.5 on wind and the EN exposure factor.
The force on a row is F = Wm · cf · kz · A · γn. The coefficient cf is the uplift coefficient of a monopitch canopy from EN 1991-1-4, Table 7.6 (it grows with tilt), kz is the roof zone factor (1 in the middle, 1.5 at the edge strip, 2 in the corner), A is the panel area of the row and γn is the reliability factor for the building class.
Uplift: the ballast needed is (Fz − 0.9 · G) / (0.9 · g), with Fz = F · cos(tilt) and G the weight of the panels (12 kg per m2). Sliding: the mass needed is (Fx / μ + Fz) / (0.9 · g) minus the panel mass, with Fx = F · sin(tilt) and μ the design friction coefficient of the surface under the supports. Ballast and panels count with a factor of 0.9 because they work in your favour.
The verdict is positive only when the ballast of the chosen supports exceeds the uplift, the sliding figure and the share of uplift carried by the most loaded support line (the rear one, with wind from behind). The friction coefficient comes from the surface: 0.40 for a PVC or TPO membrane with a rubber mat, 0.35 for compacted gravel, 0.45 for EPDM, bitumen or dry concrete, down to 0.15 for a foil-faced mat. A value you measured on site can replace it.
Step by step
- Pick the place. Choose a city or region for the wind pressure and snow, or enter your own W0 and S0 in pascals.
- Describe the roof. Enter the building height, the terrain category and the roof zone: middle, edge strip or corner.
- Describe the row. Enter the number of panels in a row, the tilt and the panel model.
- Choose the supports. Pick the ballast block, the number of layers and the surface under them, which sets the friction.
- Read the result. Compare the mass needed against uplift and against sliding with what the supports give, then repeat for the edge and the corner.
Assumptions and limits
- One row of panels on a flat roof or on the ground, wind from behind, which is the worst case for uplift. No credit for a parapet, for neighbouring rows or for shielding by other buildings.
- Panel weight is 12 kg per m2. The roof zones are the simplified factors x1, x1.5 and x2, not the full pressure coefficient maps of EN 1991-1-4.
- Friction depends on the real surface under the supports. Use the lowest value you can measure on site, and check what the membrane maker allows under ballast mats.
- The result covers wind only. Snow, the self-weight of the ballast and the load capacity of the roof are separate checks (see the snow and wind calculator).
- This is guidance for choosing and comparing layouts. It is not a design and does not replace the calculation of the engineer of record.
Worked example
Example from the calculator: Kyiv, wind pressure W0 = 370 Pa, building height 6 m, terrain category II, one row of 5 panels at 15 degrees on a PVC or TPO membrane with a rubber mat (friction 0.40), middle zone. The calculator gives 1,063 kg against uplift and 1,879 kg against sliding, so the row needs at least 1,879 kg, about 376 kg per panel.
One layer of 2PB10-1 concrete lintels (43 kg each) gives 516 kg for this row, and even three layers do not cover the need. Use heavier blocks or fix the frame mechanically.
The same row at the edge strip needs 2,895 kg and in the corner 3,912 kg. Tilt matters too: at 10 degrees the middle-zone row needs 1,297 kg, at 20 degrees 2,540 kg.
Reference table
| Roof zone | Height 6 m | Height 12 m | Height 20 m |
|---|---|---|---|
| Middle | 1,879 | 2,260 | 2,572 |
| Edge strip | 2,895 | 3,468 | 3,936 |
| Corner | 3,912 | 4,676 | 5,300 |
Every figure is the larger of the uplift and the sliding result of the calculator, for the place, terrain category and friction of the example above. Change them in the tool to get your own table.
What to check with an engineer
- The load capacity of the roof per m2 for ballast, panels, snow and maintenance, with the reserve the structure really has.
- The wind zone and terrain category of the site from the official map, and local effects such as parapets, nearby tall buildings and the roof height.
- The friction on the real surface, and whether the membrane maker approves ballast mats and block supports on that membrane.
- Whether ballast alone is acceptable, or the frame needs mechanical fixing, which is common at the edge, in the corner and on tall buildings.
- The system maker’s own wind data, because the pressure coefficients of a specific frame can differ from the generic canopy table.
The calculation is preliminary. A qualified engineer must check it before installation. Codes: DBN V.1.2-2:2006 (Ukraine) and the Eurocode; for other countries — snow and wind values from the national annex, entered by hand.
Frequently asked questions
How many kg of ballast per solar panel on a flat roof?
There is no fixed figure. For one row of 5 panels at 15 degrees in Kyiv the calculator gives 1,879 kg in the middle of the roof, about 376 kg per panel, and 3,912 kg in the corner. The result depends on wind pressure, building height, terrain, tilt, roof zone and friction.
Why do roof edges and corners need more ballast?
Wind separates at the edge of the roof and creates stronger suction on the panels there. The calculator multiplies the wind force by 1.5 at the edge strip and by 2 in the corner. In the example, the middle needs 1,879 kg, the edge 2,895 kg and the corner 3,912 kg.
Which check decides, uplift or sliding?
The larger one decides. Uplift needs enough weight to beat the vertical suction, sliding needs enough friction to resist the horizontal push. For a low tilt on a smooth membrane, sliding often governs: in the example 1,879 kg against sliding and 1,063 kg against uplift.
What friction coefficient should I use for ballast?
Use the surface under the supports: 0.40 for PVC or TPO with a rubber mat, 0.35 for compacted gravel, 0.45 for EPDM, bitumen or dry concrete, 0.15 for a foil-faced mat. A value measured on site and confirmed by the membrane maker is better than a table value.
Does a lower tilt need less ballast?
Usually yes, because the uplift coefficient grows with tilt. In the example the middle-zone row needs 1,297 kg at 10 degrees, 1,879 kg at 15 degrees and 2,540 kg at 20 degrees. A lower tilt also means shorter row spacing, so compare the layout as a whole.
Can solar panels go on a flat roof without ballast?
Only if the frame is anchored to the load-bearing structure, so that anchors take the uplift instead of weight. A free-standing ballasted system has nothing else to resist wind, so the mass must be calculated. Always confirm that the roof carries the added load.
Which standards does the calculator follow?
Loads follow DBN V.1.2-2:2006 with the canopy coefficients of EN 1991-1-4, Table 7.6. Pages for Poland, Germany and Spain apply EN 1990 and EN 1991-1-4 with the values of the national annex. Check the current edition of the standard that applies to your project.
Ground frame designer
Design the ground frame for your solar plant
The calculator’s values go to the designer: then the frame, the DBN checks and the estimate.