Aerodynamic coefficient Caer (cf)

The multiplier turning wind pressure into force on a shape; for panels Solispec takes c_f from Table 7.6 of EN 1991-1-4:2005, as cl. 9.8 of the DBN allows.

Ground frame designer

Design the ground frame for your solar plant

Solispec picks the profiles and posts, checks the frame against snow and wind to the DBN and prices it down to the last bolt.

  • No sign-up
  • Snow and wind check
  • Drawings and estimate

Definition

In the Wm formula Caer describes the shape: the same wind acts differently on a wall, a roof and a tilted panel. Under clause 9.8 of DBN V.1.2-2:2006 Caer comes from Annex I. A plus sign means pressure towards the surface, minus away from it.

For a free-standing tilted panel with wind flowing on both sides, Annex I gives no uplift coefficient. The same clause 9.8 (Change 2) helps here: where the annex does not cover a case, coefficients may be taken from reference and experimental data. The closest documented shape is the monopitch canopy of Table 7.6 of EN 1991-1-4:2005, overall force coefficients cf for an empty canopy (φ = 0):

αcf, upliftcf, downward
0°−0.5+0.2
10°−0.9+0.5
20°−1.3+0.8
25°−1.6+1.0
30°−1.8+1.2

Example: Kyiv, 30°

At 259 Pa at 2 m (type II) a 30° panel gets 1.8 · 259 = 466 Pa of uplift and 1.2 · 259 = 311 Pa downwards. Uplift is larger, so for ground tables it governs the ballast or the pile depth.

Table 7.6 ends at 30°. For steeper angles the coefficients in the engine’s table are extrapolated, and the calculation flags it.

How Solispec applies it

The Solispec engine interpolates cf by panel tilt from Table 7.6 of EN 1991-1-4:2005 and multiplies Wm by it. The uplift resultant acts d/4 from the windward edge (7.3(6), Figure 7.16 of the same standard), so the rear support takes the larger share. For roof systems the engine also applies its own roof-zone multipliers (middle 1, edge 1.5, corner 2) — reference multipliers of the engine, not set by the norm.

Ballast calculator

Norms and clauses

  • DBN V.1.2-2:2006, cl. 9.8 (Change 2), Annex I
  • EN 1991-1-4:2005, 7.3, Table 7.6, Figure 7.16

Related terms

The whole glossary

Solispec’s calculation is preliminary: for a design it has to be checked by an engineer. The values and clauses follow the current editions of the norms on the date of the page.