Norms · PN-EN 1991-1-3 + NA · Annex B

Snow load on a flat roof with PV panels: PN-EN 1991-1-3

The snow load on a flat roof with PV panels is s = μ1 · C_e · C_t · s_k to PN-EN 1991-1-3. For panels tilted up to 30° the shape coefficient is μ1 = 0.8, and under normal conditions C_e = C_t = 1.0. In Kraków (zone 3, s_k = 1.20 kN/m²) that gives 0.96 kN/m² on the panel surface and 1.44 kN/m² as the design value. Drifts behind the panel rows and at parapets come on top and can exceed it; the rest of the page covers them.

Updated:

Formula and coefficients

  • s_k is the ground snow load from the zone and altitude (national annex, five zones); the zone values are on the page “Snow and wind zones in Poland”
  • μ1 = 0.8 for tilt up to 30°, falling linearly to 0 at 60°; panels set on a flat roof at 10° to 15° fall in the first range
  • C_e = 1.0 for normal topography (0.8 for windswept and 1.2 for sheltered sites are for the designer to choose with a reason) and C_t = 1.0 with no thermal reduction
  • design value to EN 1990: γ_Q = 1.5 for variable actions
  • snow is a variable action and never counts in the ballast as a favourable weight

Drifts at panel rows and parapets

The uniform s = μ1 · s_k describes snow lying freely. A row of panels, a parapet or any other obstruction stops wind-borne snow, so a drift builds next to it. Annex B of EN 1991-1-3 (B.2, drifting at projections and obstructions) gives the pattern: μ1 = 0.8 on the windward side and μ2 = γ · h / s_k on the leeward side, where h is the height of the obstruction, γ = 2 kN/m³ and μ2 stays between 0.8 and 2.0.

EN 1991-1-3 has no separate rule for PV panel rows. A designer applies Annex B by analogy with an obstruction when the rows are continuous and high; for rows with gaps and low rows the extent of the drift is the designer’s judgement. The Solispec calculator works out the uniform s = μ1 · s_k and does not compute drifts; the designer adds them separately.

The table gives the drift load s = μ2 · s_k at an obstruction 0.5 m and 1.0 m high for the snow zones up to 300 m above sea level. With a small s_k and a low obstruction the lower limit μ2 = 0.8 governs, so the drift equals the uniform load on the roof (without the μ1 reduction):

Zones_k, kN/m²on the panel 0.8 · s_k, kN/m²drift, h = 0.5 m, kN/m²drift, h = 1.0 m, kN/m²
10.700.561.001.40
20.900.721.001.80
31.200.961.002.00
41.601.281.282.00
52.001.601.602.00

Worked example: Kraków

Kraków lies at 219 m above sea level, in snow zone 3, s_k = 1.20 kN/m². On a panel tilted up to 30° s = 0.8 · 1.20 = 0.96 kN/m², design value 1.44 kN/m². Behind a row 0.5 m high μ2 = 2 · 0.5 / 1.20 = 0.83, so the drift load is 1.00 kN/m² (design value 1.50 kN/m²); at 1.0 m height μ2 reaches the upper limit of 2.0, which gives 2.00 kN/m².

Ballast and roof capacity

  • ballast is sized for wind (uplift and sliding), not for snow; snow must not be counted as ballast
  • the roof must carry the weight of ballast and snow together, including the local drift under a row; the building’s structural engineer, who knows the capacity of the deck, checks this
  • when combining actions Solispec takes ψ0 = 0.5 for snow (up to 1000 m above sea level) and ψ0 = 0.6 for wind, so snow and wind do not act at full value at once
  • on a roof with little reserve, a steeper panel or a layout parallel to the roof pitch lowers the ballast, and limits both wind and drifts

Checklist for the design

  • County and the building’s altitude noted, the snow zone read from the national annex
  • s_k from the zone formula, cross-checked with the tables on the page “Zones in Poland”
  • Panel tilt checked: up to 30° μ1 = 0.8
  • Height of the rows and parapets set, drifts to Annex B calculated or justified by the absence of an obstruction
  • Design values with γ_Q = 1.5 and the combination with ψ0 to EN 1990
  • Roof capacity checked for ballast, panels and snow together with the drift
  • Design checked by a structural engineer

Frequently asked questions

How is the snow load on a flat roof with PV panels calculated?

To PN-EN 1991-1-3: s = μ1 · C_e · C_t · s_k. For panels tilted up to 30° μ1 = 0.8 and C_e = C_t = 1.0. In Kraków, with s_k = 1.20 kN/m², that is 0.96 kN/m².

Do PV panels change the snow load on the roof?

Yes, in two ways: the panels change the shape of the lying snow, so drifts can build next to the rows, and the weight of the panels and ballast is added. The structural engineer checks the roof for all of it together.

How big is the drift at a panel row?

Annex B.2 gives μ2 = γ · h / s_k, with γ = 2 kN/m³, between 0.8 and 2.0. For a row 0.5 m high in Kraków that is 1.00 kN/m²; the table on the page gives zones 1 to 5.

Can snow be counted in the ballast?

No. Ballast is a permanent weight sized for wind; snow is a variable action that may be absent, so it is not counted as a favourable weight.

Is this page enough for a structural design?

No. It shows the method and guide values. A structural engineer does the calculation for the building to the country’s standards.

Sources: the standards

  • PN-EN 1991-1-3:2005 + NA (+AC:2009, Ap1:2010), Eurokod 1: Oddziaływania na konstrukcje, Część 1-3: Oddziaływania ogólne, Obciążenie śniegiem (5.2, załącznik B)
  • PN-EN 1991-1-4:2008 + NA, Eurokod 1: Oddziaływania na konstrukcje, Część 1-4: Oddziaływania ogólne, Oddziaływania wiatru
  • PN-EN 1990:2004 + NA, Eurokod: Podstawy projektowania konstrukcji

The values are guide values. The extent of the drift behind panel rows and the capacity of the roof are for a structural engineer to assess for the actual building.