Glossary · Lightning, earthing, fire safety

Surge protective device (SPD)

A device that limits lightning and switching surges in PV circuits; its type depends on whether the building has lightning protection.

Ground frame designer

Design the ground frame for your solar plant

Solispec picks the profiles and posts, checks the frame against snow and wind to the DBN and prices it down to the last bolt.

  • No sign-up
  • Snow and wind check
  • Drawings and estimate

Definition

Long DC cables on a roof act as an antenna: a nearby lightning strike induces a pulse in them that can break down the inverter input. A surge protective device (SPD) diverts that pulse to earth. DBN V.2.5-23:2025 (cl. 8.6) requires protection against lightning and induced surges with SPDs per DSTU EN 62305-4:2012 and the device standards.

For the PV part, section 712.534 of DSTU HD 60364-7-712:2022 sets where and which SPDs go. The key question is whether the building has external lightning protection (LPS). If it does, the array either keeps the separation distance from the down conductors or is bonded to the LPS, and then part of the lightning current can flow through its circuits. In that case the DC side needs a type 1+2 SPD and a 16 mm² Cu bonding conductor (cl. 712.534.101, 712.534.105).

An SPD does not replace earthing: without a short path to the main earthing bar it has nowhere to send the pulse. And the need for external lightning protection is decided by a risk assessment, not by the presence of a PV array.

Where SPDs go. Usually at the inverter DC input or in a DC combiner next to it, and on the AC side in the building's distribution board, since the inverter is tied to the grid as well. A DC SPD's rated voltage must match the string's UOC MAX. Keep the conductor from the SPD to the earthing bar as short as possible and without loops. The device type depends on the building's lightning protection: without an LPS, or with the separation distance kept, the requirements are milder than when the frame is bonded to the LPS. The final choice of devices and locations is made in the electrician's design.

How Solispec applies it

When the Solispec constructor is told the building has lightning protection, the electrical check adds a line: separation distance per DSTU EN 62305-3:2021 or bonding to the LPS, SPD type 1+2, 16 mm² Cu conductor (712.534.101, 712.534.105). The report’s fire and lightning section computes the separation distance from your inputs and, if it is not met, advises bonding the frame to the LPS and fitting a type 1+2 DC SPD.

Solispec constructor

Norms and clauses

Related terms

The whole glossary

Solispec’s calculation is preliminary: for a design it has to be checked by an engineer. The values and clauses follow the current editions of the norms on the date of the page.