Nominal discharge current of an SPD In

The peak of the 8/20 µs current impulse an SPD of test class II (type 2) withstands repeatedly without damage; typically 5–20 kA per pole.

Updated:

Definition

The nominal discharge current In is a datasheet parameter of an SPD: the peak of a current impulse of the 8/20 µs shape (8 µs to the crest, 20 µs to half value) that the device passes many times in a row and stays serviceable. The device standard DSTU EN 61643-11:2016 (the adopted IEC 61643-11) defines it: In classifies an SPD of test class II, and in the test itself the In impulse is applied to the device in series — 15 impulses — after which its characteristics are checked for change. The maker gives In per protection mode (L–N, L–PE, N–PE) or as a total.

In is read together with two neighbouring parameters. Imax is the maximum discharge current of the same 8/20 µs shape the device withstands once; it is usually twice In. Iimp is the impulse current of the 10/350 µs shape for an SPD of test class I (type 1): the share of the lightning current that flows through the device when the PV frame is bonded to the lightning protection. The voltage protection level Up is stated by the maker at In: the more current passes, the higher the voltage at the terminals, so Up must stay below the impulse withstand of the inverter input.

SPDImpulseTypical values
Type 2 (class II), AC sideIn, 8/20 µs5–20 kA per pole; Imax 20–40 kA
Type 2 (class II), PV DC sideIn, 8/20 µs5–20 kA per pole, mostly 15–20 kA
Type 1+2 (class I + II)Iimp, 10/350 µs and InIimp 12.5–25 kA per pole; In 20–25 kA

What In means for a PV plant. The device type follows the building’s lightning protection (section 712.534 of DSTU HD 60364-7-712:2022): without external lightning protection, or with the separation distance kept, a type 2 SPD is enough, and low-voltage installation practice takes In of at least 5 kA as the lower limit; when the frame is bonded to the LPS, a type 1+2 device with Iimp of at least 12.5 kA per pole is needed. For the DC side a device rated for direct current is chosen, with a rated voltage not below the string’s UOC MAX. A higher In means more margin and a longer life of the varistor: every impulse wears it a little, and a device with In 20 kA outlives one with 5 kA by about twice as many storms, other things equal.

What In does not tell. It does not say how much lightning current the device takes on a direct strike — that is Iimp; it does not replace earthing (without a short conductor to the bar the SPD has nowhere to send the pulse); and it is not a norm requirement for a given PV plant — the risk assessment decides whether external lightning protection is needed, and the device type and current follow from that.

How Solispec applies it

The Solispec constructor names the SPD type, not its current: when the building is marked as having lightning protection, the electrical check adds a line on the separation distance or bonding to the LPS, an SPD type 1+2 and a 16 mm² Cu conductor; without lightning protection — type 2. The report compares the DC SPD’s rated voltage with the string’s UOC MAX. The In and Iimp of the actual device are chosen in the electrical design from the maker’s datasheet — the report says so in its fire and lightning section.

Solispec constructor

Ground frame designer

Design the ground frame for your solar plant

Solispec picks the profiles and posts, checks the frame against snow and wind to the DBN and prices it down to the last bolt.

Norms and clauses

Frequently asked questions

What is nominal discharge current of an SPD In?

The peak of the 8/20 µs current impulse an SPD of test class II (type 2) withstands repeatedly without damage; typically 5–20 kA per pole. The nominal discharge current In is a datasheet parameter of an SPD: the peak of a current impulse of the 8/20 µs shape (8 µs to the crest, 20 µs to half value) that the device passes many times in a row and stays serviceable.

Which norm defines nominal discharge current of an SPD In?

DSTU EN 61643-11:2016; DSTU HD 60364-7-712:2022, section 712.534.

How does Solispec calculate nominal discharge current of an SPD In?

The Solispec constructor names the SPD type, not its current: when the building is marked as having lightning protection, the electrical check adds a line on the separation distance or bonding to the LPS, an SPD type 1+2 and a 16 mm² Cu conductor; without lightning protection — type 2. The report compares the DC SPD’s rated voltage with the string’s UOC MAX. Solispec constructor: /app