Glossary · Lightning, earthing, fire safety

Combustible roofs and PV cables

NAPB forbids external wiring over combustible roofs; on bitumen shingle or onduline, DC cables run in metal trays or conduit.

Ground frame designer

Design the ground frame for your solar plant

Solispec picks the profiles and posts, checks the frame against snow and wind to the DBN and prices it down to the last bolt.

  • No sign-up
  • Snow and wind check
  • Drawings and estimate

Definition

The Fire Safety Rules of Ukraine, NAPB A.01.001-2014 (section IV, ch. 1, cl. 1.18), forbid external wiring over combustible roofs. PV cables on a roof are external wiring, so on a roof of combustible materials (bitumen shingle on OSB, onduline and the like) they cannot simply lie on the covering.

The rule does not explain exactly how it applies to cables under an array. The practical answer is metal trays or conduit and penetrations of non-combustible materials. Whether your roof is combustible is set by the combustibility group of its surface layer on the maker’s certificate; the groups are classified in DBN V.1.1-7:2016 (Annex A). Do not guess the group from the material name.

Ukrainian norms set no fire setbacks from roof edges, no access paths between arrays, no mandatory rapid shutdown and no firefighter signage for rooftop PV. SES guidelines recommend a diagram showing the disconnection point placed near it, but that is a recommendation. What remains mandatory are the rules on penetrations, on wiring over combustible roofs and on lightning protection by risk assessment.

What it looks like in practice. On a soft roof or onduline, the cable from the string to the descent runs in a metal tray or metal conduit, and the cable entry under the roof goes through a penetration of non-combustible materials. Think separately about where the inverter and DC combiner go: NAPB (section IV, ch. 1, cl. 1.18) forbids storing combustible materials closer than 1 m to electrical equipment and under switchboards. The Solispec pitched-roof attachment calculator takes the covering into account for the fixings, and the fire warnings appear in the constructor's full report.

How Solispec applies it

You choose the roof covering in the Solispec constructor. For combustible coverings the engine shows a warning citing NAPB: run DC cables in metal trays or conduit, not on the roof; penetrations of non-combustible materials; check the combustibility group against the certificate (DBN V.1.1-7:2016 Annex A). The engine adds no fire setbacks: wind and structural edge distances are in the calculation, fire setbacks are set by no norm.

Roof attachment calculator

Norms and clauses

  • NAPB A.01.001-2014, section IV, ch. 1, cl. 1.18
  • DBN V.1.1-7:2016, Annex A

Related terms

The whole glossary

Solispec’s calculation is preliminary: for a design it has to be checked by an engineer. The values and clauses follow the current editions of the norms on the date of the page.