What DC cable do you need from solar panels to the inverter: cross-section calculator
Choose the panel, panels in a string, strings on one cable and the run length one way. The calculator shows the smallest copper cross-section, the voltage drop and the current check.
Updated:
For a string of 9 panels (375 V, 13.2 A) and a run of 30 m one way, a 4 mm² cable is enough: a voltage drop of 1.11 % against a target of 1.5 %. Up to 40 m 4 mm² works, up to 61 m 6 mm², up to 101 m 10 mm².
How the calculator works
The calculator takes the electrical data of the panel from the catalogue (the voltage U_mp and the currents I_mp and I_SC) and computes the voltage drop on the cable of one string: ΔU = 2 · L · I_mp · ρ / S / (n · U_mp). L is the length one way, S the cross-section, n the number of panels in the string and ρ the resistivity of copper at 70 °C: 0.0175 · (1 + 0.00393 · 50) ≈ 0.0209 Ω·mm²/m. HD 60364-7-712 (cl. 712.523.101) asks for 70 °C for cables under the panels.
Of the sections 4, 6 and 10 mm² the smallest with ΔU within the target is taken. The 1.5 % target is the app target, not a requirement: in the standards we hold there is no voltage drop limit for PV direct-current circuits.
Then the current check (cl. 712.433.101). The design current is I_SC MAX = 1.25 · I_SC · the number of strings on the cable. The current rating I_z comes from the maker datasheet of an H1Z2Z2-K cable (EN 50618) for two cables side by side on a surface: 44, 57 and 79 A for 4, 6 and 10 mm², times 0.91 for 70 °C. If I_z is below the design current, the section goes up, to 16 mm².
This is the same logic as the electrics check of the Solispec designer (HD 60364-7-712, with the national adoption and rules of the country). Strings in parallel on one cable are treated as joined before a common cable that carries their sum; if each string has its own cable, the current of one string is enough.
Step by step
- Choose the panel. U_mp, I_mp and I_SC of the panel come from the catalogue.
- Describe the string. How many panels in series, and how many strings run in parallel on one cable.
- Enter the length. The cable length one way from the panels to the inverter, with every bend and drop.
- Set the allowed drop. The app target is 1.5 %; a smaller drop means a thicker cable and less loss.
- Read the result. The smallest cross-section, the voltage drop on it and the check against the cable current rating.
Assumptions and limits
- A copper conductor, an H1Z2Z2-K type cable, 70 °C under the panels.
- The current rating is the maker data for two cables side by side on a surface, times 0.91; check it against the datasheet of your cable.
- The drop is computed on the cable of one string with its current I_mp; the current check takes the sum of the strings on a common cable.
- The 1.5 % is an app target, not a limit from a standard.
- The calculator does not count grouping in a bundle, trays with several cables or shading of the cable.
Worked example
Example: 2 strings of 9 panels of 550 W (9.9 kW). A string gives 375 V and 13.2 A, and the run is 30 m one way. The voltage drop is 1.11 % at 4 mm², 0.74 % at 6 mm² and 0.44 % at 10 mm². The smallest section within 1.5 % is 4 mm².
The current check: 2 strings on the cable give I_SC MAX = 1.25 · 13.9 · 2 = 34.8 A. The rating of a 4 mm² cable is 40.0 A, so 34.8 A fits. With 3 strings on one cable the current is 52.1 A, and the current raises the section to 10 mm².
The length limits for this string: 4 mm² works up to 40 m, 6 mm² up to 61 m and 10 mm² up to 101 m. Beyond that even 10 mm² does not meet 1.5 %: a shorter run, a longer string or a larger allowed drop.
Reference table
| Length one way, m | Drop at 4 mm², % | Drop at 6 mm², % | Drop at 10 mm², % | Smallest section |
|---|---|---|---|---|
| 10 | 0.37 | 0.25 | 0.15 | 4 mm² |
| 20 | 0.74 | 0.49 | 0.29 | 4 mm² |
| 30 | 1.11 | 0.74 | 0.44 | 4 mm² |
| 50 | 1.84 | 1.23 | 0.74 | 6 mm² |
| 80 | 2.95 | 1.97 | 1.18 | 10 mm² |
| 100 | 3.69 | 2.46 | 1.47 | 10 mm² |
Copper at 70 °C, I_mp 13.2 A, string 375 V, target 1.5 %. The drop grows in proportion to the length and falls in inverse proportion to the section.
What to check with an engineer
- The datasheet of the chosen cable: the current rating for your way of laying; the calculator uses maker data for H1Z2Z2-K, two cables side by side on a surface.
- The way of laying: in a tray, in conduit, under the roof covering or in a bundle with other cables lowers the current rating.
- The maximum system voltage and the string protection: gPV fuses when three or more strings run in parallel.
- The real length of the run with every bend and vertical section, not the plan length.
- The rules of your country for direct-current circuits and lightning protection.
The calculation is preliminary. A qualified engineer must check it before installation. Codes: DBN V.1.2-2:2006 (Ukraine) and the Eurocode; for other countries — snow and wind values from the national annex, entered by hand.
Frequently asked questions
What cable do I need from solar panels to the inverter over 30 metres?
For a string of 9 panels (375 V, 13.2 A) and a run of 30 m one way, 4 mm² is enough: a drop of 1.11 %. With several strings on one cable the section is also checked against the current: 3 strings need 10 mm². Enter your own panel in the calculator.
What DC cable cross-section for 10 kW of panels?
The section depends on the string current and the run length, not on kilowatts. In the example 2 strings of 9 panels (9.9 kW) give 13.2 A per string: 4 mm² works up to 40 m, 6 mm² up to 61 m, 10 mm² up to 101 m. Work out longer runs separately.
Is 4 mm² enough for solar panels?
In this example yes: by voltage drop up to 40 m, and by current while the cable carries no more than two strings (40.0 A rating against 34.8 A design current). Longer runs or three strings on one cable need 6 or 10 mm².
What voltage drop is allowed in a DC cable?
In the standards we hold (HD 60364-7-712) there is no voltage drop limit for PV direct-current circuits. The calculator uses an app target of 1.5 %, which you can change. A smaller drop means less energy lost but a thicker cable.
Why is the DC cable sized at 70 °C?
Cables under the panels are heated from below, so HD 60364-7-712 (cl. 712.523.101) asks for an ambient temperature of at least 70 °C for them. At 70 °C the resistance of copper is about 20 % higher than at 20 °C, so the drop is larger than in a cool place.
Ground frame designer
Design the ground frame for your solar plant
The calculator’s values go to the designer: then the frame, the DBN checks and the estimate.