What DC cable do you need from solar panels to the inverter: cross-section calculator

Choose the panel, panels in a string, strings on one cable and the run length one way. The calculator shows the smallest copper cross-section, the voltage drop and the current check.

Updated:

For a string of 9 panels (375 V, 13.2 A) and a run of 30 m one way, a 4 mm² cable is enough: a voltage drop of 1.11 % against a target of 1.5 %. Up to 40 m 4 mm² works, up to 61 m 6 mm², up to 101 m 10 mm².

How the calculator works

The calculator takes the electrical data of the panel from the catalogue (the voltage U_mp and the currents I_mp and I_SC) and computes the voltage drop on the cable of one string: ΔU = 2 · L · I_mp · ρ / S / (n · U_mp). L is the length one way, S the cross-section, n the number of panels in the string and ρ the resistivity of copper at 70 °C: 0.0175 · (1 + 0.00393 · 50) ≈ 0.0209 Ω·mm²/m. HD 60364-7-712 (cl. 712.523.101) asks for 70 °C for cables under the panels.

Of the sections 4, 6 and 10 mm² the smallest with ΔU within the target is taken. The 1.5 % target is the app target, not a requirement: in the standards we hold there is no voltage drop limit for PV direct-current circuits.

Then the current check (cl. 712.433.101). The design current is I_SC MAX = 1.25 · I_SC · the number of strings on the cable. The current rating I_z comes from the maker datasheet of an H1Z2Z2-K cable (EN 50618) for two cables side by side on a surface: 44, 57 and 79 A for 4, 6 and 10 mm², times 0.91 for 70 °C. If I_z is below the design current, the section goes up, to 16 mm².

This is the same logic as the electrics check of the Solispec designer (HD 60364-7-712, with the national adoption and rules of the country). Strings in parallel on one cable are treated as joined before a common cable that carries their sum; if each string has its own cable, the current of one string is enough.

Step by step

  1. Choose the panel. U_mp, I_mp and I_SC of the panel come from the catalogue.
  2. Describe the string. How many panels in series, and how many strings run in parallel on one cable.
  3. Enter the length. The cable length one way from the panels to the inverter, with every bend and drop.
  4. Set the allowed drop. The app target is 1.5 %; a smaller drop means a thicker cable and less loss.
  5. Read the result. The smallest cross-section, the voltage drop on it and the check against the cable current rating.

Assumptions and limits

  • A copper conductor, an H1Z2Z2-K type cable, 70 °C under the panels.
  • The current rating is the maker data for two cables side by side on a surface, times 0.91; check it against the datasheet of your cable.
  • The drop is computed on the cable of one string with its current I_mp; the current check takes the sum of the strings on a common cable.
  • The 1.5 % is an app target, not a limit from a standard.
  • The calculator does not count grouping in a bundle, trays with several cables or shading of the cable.

Worked example

Example: 2 strings of 9 panels of 550 W (9.9 kW). A string gives 375 V and 13.2 A, and the run is 30 m one way. The voltage drop is 1.11 % at 4 mm², 0.74 % at 6 mm² and 0.44 % at 10 mm². The smallest section within 1.5 % is 4 mm².

The current check: 2 strings on the cable give I_SC MAX = 1.25 · 13.9 · 2 = 34.8 A. The rating of a 4 mm² cable is 40.0 A, so 34.8 A fits. With 3 strings on one cable the current is 52.1 A, and the current raises the section to 10 mm².

The length limits for this string: 4 mm² works up to 40 m, 6 mm² up to 61 m and 10 mm² up to 101 m. Beyond that even 10 mm² does not meet 1.5 %: a shorter run, a longer string or a larger allowed drop.

Reference table

Voltage drop on the cable of a string by run length and cross-section, example of 9 panels of 550 W
Length one way, mDrop at 4 mm², %Drop at 6 mm², %Drop at 10 mm², %Smallest section
100.370.250.154 mm²
200.740.490.294 mm²
301.110.740.444 mm²
501.841.230.746 mm²
802.951.971.1810 mm²
1003.692.461.4710 mm²

Copper at 70 °C, I_mp 13.2 A, string 375 V, target 1.5 %. The drop grows in proportion to the length and falls in inverse proportion to the section.

What to check with an engineer

  • The datasheet of the chosen cable: the current rating for your way of laying; the calculator uses maker data for H1Z2Z2-K, two cables side by side on a surface.
  • The way of laying: in a tray, in conduit, under the roof covering or in a bundle with other cables lowers the current rating.
  • The maximum system voltage and the string protection: gPV fuses when three or more strings run in parallel.
  • The real length of the run with every bend and vertical section, not the plan length.
  • The rules of your country for direct-current circuits and lightning protection.

The calculation is preliminary. A qualified engineer must check it before installation. Codes: DBN V.1.2-2:2006 (Ukraine) and the Eurocode; for other countries — snow and wind values from the national annex, entered by hand.

Frequently asked questions

What cable do I need from solar panels to the inverter over 30 metres?

For a string of 9 panels (375 V, 13.2 A) and a run of 30 m one way, 4 mm² is enough: a drop of 1.11 %. With several strings on one cable the section is also checked against the current: 3 strings need 10 mm². Enter your own panel in the calculator.

What DC cable cross-section for 10 kW of panels?

The section depends on the string current and the run length, not on kilowatts. In the example 2 strings of 9 panels (9.9 kW) give 13.2 A per string: 4 mm² works up to 40 m, 6 mm² up to 61 m, 10 mm² up to 101 m. Work out longer runs separately.

Is 4 mm² enough for solar panels?

In this example yes: by voltage drop up to 40 m, and by current while the cable carries no more than two strings (40.0 A rating against 34.8 A design current). Longer runs or three strings on one cable need 6 or 10 mm².

What voltage drop is allowed in a DC cable?

In the standards we hold (HD 60364-7-712) there is no voltage drop limit for PV direct-current circuits. The calculator uses an app target of 1.5 %, which you can change. A smaller drop means less energy lost but a thicker cable.

Why is the DC cable sized at 70 °C?

Cables under the panels are heated from below, so HD 60364-7-712 (cl. 712.523.101) asks for an ambient temperature of at least 70 °C for them. At 70 °C the resistance of copper is about 20 % higher than at 20 °C, so the drop is larger than in a cool place.

Embed on your website

Free. Paste this code into your page and the calculator runs on your site, with no cookies and no data collected.

<script src="https://solispec.com/widget.js" async></script>