Ballast for a flat-roof solar array: kg per panel (Krakow)

How many kg of ballast a row of 10 panels needs on a flat roof in Krakow: uplift and sliding, roof zone, tilt and building height. Every number comes from the Solispec engine, with steps to repeat it.

By Solispec editorial3 min read

One row of 10 panels at 10 degrees on a flat roof in Krakow, 10 m up, needs about 3715 kg of ballast in the middle of the roof: 371 kg per panel, or 144 kg per m² of panel area. Sliding decides, not uplift (2483 kg). The edge strip needs 5728 kg and the corner 7740 kg.

Every figure below comes from the same engine functions behind the free ballast calculator, so you can repeat it with your own data. The wind and snow for a city are in the snow and wind calculator, and the general logic of fixing is in the article on roof mounting.

Starting data

ItemValue
PlaceKrakow, wind W0 300 Pa, snow S0 1200 Pa (Polish national annex values)
Buildingflat roof, 10 m above ground, terrain category II
Row10 panels of 2350 × 1100 mm (550 W), 25.85 m² of panels, tilt 10°
SurfacePVC or TPO membrane with a rubber mat, friction μ 0.40
Supportsone layer of 2PB10-1 concrete lintels, 43 kg each, wind from behind, middle of the roof

What the ballast has to resist

CheckBallast needed
Wind uplift2483 kg
Sliding3715 kg
Needed (the larger)3715 kg
One layer of lintels gives516 kg
Three layers give1548 kg

Sliding decides here: at a low tilt the wind pushes the row sideways more than it lifts it, and the friction of the membrane is only 0.40. 3715 kg over 10 panels is 371 kg per panel. One layer of lintels (516 kg) is far from enough, and so are three (1548 kg), so the row needs heavier blocks, a mechanical fixing or a different layout.

What changes the result

Roof zone10°15°20°
Middle3715 kg5309 kg7112 kg
Edge strip5728 kg8118 kg10823 kg
Corner7740 kg10928 kg14534 kg

The edge strip multiplies the wind force by 1.5 and the corner by 2. Building height matters less: in the middle at 10° the row needs 3221 kg at 6 m, 3902 kg at 12 m and 4454 kg at 20 m.

How to repeat the calculation

  1. Open the ballast calculator, pick Krakow and enter the wind and snow of the city in pascals (300 and 1200).
  2. Set one row of 10 panels, tilt 10°, building height 10 m, terrain category II and the middle zone.
  3. Compare with the tables above, then change the zone and the tilt.

The calculation is preliminary. The wind is taken from behind with no credit for a parapet or neighbouring rows, so the figure is on the safe side. Snow, the load capacity of the roof and the friction of the real surface are separate checks. Before installation the calculation must be checked by a qualified engineer, and the installation must be done only by a qualified electrician.

FAQ

How many kg of ballast per solar panel on a flat roof?

For a row of 10 panels at 10 degrees in Krakow, 371 kg per panel in the middle of the roof and 774 kg in the corner. There is no single figure: it depends on the wind, building height, tilt, roof zone and friction.

Does a lower tilt need less ballast?

Yes. In the middle zone the row needs 3715 kg at 10 degrees, 5309 kg at 15 and 7112 kg at 20.

Can the roof carry that much ballast?

The engine does not check it. 144 kg per m² of panel area is a large extra load for many flat roofs, so an engineer must check the load capacity of the roof before the layout is chosen.

StructuresNorms

News and design tips

What’s new in Solispec, changes to the standards and practical tips on designing solar power systems.

What interests you

How we handle your data: privacy policy.

Ground frame designer

Design the ground frame for your solar plant

Solispec picks the profiles and posts, checks the frame against snow and wind to the DBN and prices it down to the last bolt.

  • No sign-up
  • Snow and wind check
  • Drawings and estimate