Worked check, 2026

Worked check: Solispec against a hand calculation, step by step

Three cases from three countries, each done twice: by hand from the formulas and tables of the standard, and by the Solispec engine with the same inputs. The inputs, the clause of each step and both results are in the tables. The results are preliminary and an engineer must verify them.

In the browser, nothing to install, no card: the Start plan is free.

Ground frame designer

Design the ground frame for your solar plant

Solispec picks the profiles and posts, checks the frame against snow and wind to the DBN and prices it down to the last bolt.

What was checked, and how to read the tables

Each table has four columns: the step, the formula with the clause it comes from, the result of the hand calculation, and the result Solispec gives for the same input. The hand calculation uses only the formulas and tables of the standards and a calculator; it does not call the Solispec code. The rounding is stated above each table, and the figures agree at that rounding.

This is a check of the arithmetic and of the chain of coefficients that Solispec applies. It is not a third-party validation and it does not replace the engineer who verifies the design for the site. Where Solispec simplifies a standard, the case says so. The page is tested: an automated test recomputes every number on it from the engine, so the build fails if the engine changes and the page does not.

Case 1: Ukraine, Kyiv, a ground frame

A ground-mounted table in Kyiv, with loads by DBN V.1.2-2:2006 with Changes No. 1 and No. 2. The panel coefficients are the engine’s own: the canopy values of EN 1991-1-4 Table 7.6, which clause 9.8 of the DBN allows where its annexes have none for a PV canopy. Those coefficients are defined on the peak pressure, so the wind on them takes the exposure factor c_e(z) of EN 1991-1-4 4.5 instead of C_h of Table 9.01, and W₀ (the mean pressure, clause 9.6) is taken as the basic pressure q_b. The inputs:

Kyiv, ground frame at 30 degrees: snow and wind

Rounded to 1 Pa; the pressures on the panel plane to 0.1 Pa.

StepFormula and clauseHand resultSolispec
Characteristic snow load S0DBN V.1.2-2 table of regions, Kyiv1550 Pa1550 Pa
Snow shape coefficient μAnnex Zh, scheme 1: μ = (60 − α) / 35 for 25° < α < 60°, so (60 − 30) / 350.8570.857
Design snow load SS = γfm · S0 · Calt · μ = 1.00 · 1550 · 1.00 · 0.857 (clauses 8.2 and 8.5, Table 8.1)1329 Pa1329 Pa
Characteristic wind pressure W0DBN V.1.2-2 table of regions, Kyiv370 Pa370 Pa
Exposure factor c_e(z)EN 1991-1-4 4.5, category II (terrain type II), z = 1.51 m is below z_min = 2 m, so c_e(2 m) = (1 + 7/ln 40)·(0.19·ln 40)²1.4231.423
Design wind pressure WmWm = γfm · W0 · c_e(z) · Calt = 1.00 · 370 · 1.4234 · 1.00 (clause 9.1, Table 9.1; the EN 1991-1-4 coefficients are defined on the peak pressure, DBN 9.8)527 Pa527 Pa
Wind uplift on the panel planeEN 1991-1-4 Table 7.6, canopy at 30°: cf = 1.8 upward, so 526.7 · 1.8948.0 Pa948.0 Pa
Wind pressure down on the panel planethe same table: cf = 1.2 downward, so 526.7 · 1.2632.0 Pa632.0 Pa

Checked November 6, 2026

Case 2: Poland, Krakow, a flat roof with ballast

A row of five panels on the flat roof of a 6 m building in Krakow. Snow and wind are the values of the Polish national annex at the city; the loads are combined by EN 1990 with the factor 1.5 on wind and 0.9 on the weight that holds the row down. The ballast is checked for uplift and for sliding. The inputs:

Krakow, flat roof, 5 panels at 10 degrees: loads and ballast

Rounded to 1 kg, 1 N and 1 Pa; coefficients to three decimals.

StepFormula and clauseHand resultSolispec
Characteristic snow load s_kPN-EN 1991-1-3 national annex, zone 3: s_k = max(1.2; 0.006 · A − 0.6) at A = 219 m1.200 kN/m², 1200 Pa1200 Pa
Basic wind pressure q_bPN-EN 1991-1-4 national annex, zone 1, A ≤ 300 m: v_b,0 = 22 m/s, q_b = 0.30 kN/m² (Table NA.1)300 Pa300 Pa
Design snow loadEN 1990 factor 1.5, EN 1991-1-3 Table 5.2: μ1 = 0.8 up to 30°, so 1.5 · 1200 · 0.81440 Pa1440 Pa
Exposure factor c_e at 6.65 mEN 1991-1-4 4.5, category II: z0 = 0.05 m, k_r = 0.19, c_e = (1 + 7 / ln(z / z0)) · (k_r · ln(z / z0))²2.0992.099
Design wind pressure Wm1.5 · 300 · 2.099945 Pa945 Pa
Wind force on the rowF = Wm · cf · kz · A · γn, with cf = 0.9 uplift at 10° (EN 1991-1-4 Table 7.6): 944.5 · 0.9 · 1.0 · 12.925 · 1.010987 N10987 N
Components of the forceFz = F · cos 10°, Fx = F · sin 10°Fz 10820 N, Fx 1908 NFz 10820 N, Fx 1908 N
Ballast against uplift(Fz − 0.9 · G · g) / (0.9 · g), with G = 12.925 · 12 = 155.1 kg1070 kg1070 kg
Ballast against sliding(Fx / μ + Fz) / (0.9 · g) − G, with μ = 0.401611 kg1611 kg
Ballast the row needsthe larger of the two; sliding governs here1611 kg1611 kg
Uplift at the most loaded supportresultant d/4 from the windward edge (EN 1991-1-4 7.3(6), Figure 7.16): share 0.836 on the rear line; 1070 / 6 frames · 0.836149 kg per frame149 kg per frame

Checked November 6, 2026

Case 3: Germany, Munich, a ground frame

A ground-mounted table in Munich: the snow and wind values of the German national annex at the city, combined by EN 1990 with the factor 1.5, on the panel plane at 30 degrees. The inputs:

Munich, ground frame at 30 degrees: snow and wind

Rounded to 1 Pa; the pressures on the panel plane to 0.1 Pa.

StepFormula and clauseHand resultSolispec
Characteristic snow load s_kDIN EN 1991-1-3/NA, zone 1a = 1.25 × zone 1; zone 1: s_k = 0.19 + 0.91 · ((A + 140) / 760)² = 0.885 at A = 524 m; 1.25 · 0.8851.106 kN/m², 1110 Pa1110 Pa
Basic wind pressure q_bDIN EN 1991-1-4/NA, zone 2: q_b = 0.39 kN/m², no altitude factor below 800 m390 Pa390 Pa
Design snow loadEN 1990 factor 1.5, EN 1991-1-3 Table 5.2: μ1 = 0.8 up to 30°, so 1.5 · 1110 · 0.81332 Pa1332 Pa
Exposure factor c_eEN 1991-1-4 4.5, category II; z = 1.51 m is below the minimum 2 m, so z = 2 m: (1 + 7 / ln(2 / 0.05)) · (0.19 · ln(2 / 0.05))²1.4231.423
Design wind pressure Wm1.5 · 390 · 1.423832.7 Pa832.7 Pa
Wind on the panel planeEN 1991-1-4 Table 7.6 at 30°: cf = 1.8 uplift, 1.2 down; 832.7 · 1.8 and 832.7 · 1.21498.9 Pa up, 999.2 Pa down1498.9 Pa up, 999.2 Pa down

Checked November 6, 2026

What the check does not prove

Agreement with a hand calculation shows that Solispec applies the formulas, tables and factors it states, and applies them correctly. It does not show more than that:

Where to go next

Questions

Has Solispec been tested for accuracy by an independent party?

Not by a third party, and we do not claim it. What we publish instead is this check: three cases recomputed by hand from the standards, with the inputs, the clauses and both results, and an automated test that recomputes every number here from the engine. Repeat them in the free calculators, and have an engineer verify any real project.

Can I repeat these numbers myself?

Yes. Enter the inputs listed above each table in the snow and wind calculator and the ballast calculator, with the annex values of the city where the country needs them. The calculators run the same engine as the designer, so the results match the tables.

Which standards do the loads follow?

Ukraine: DBN V.1.2-2:2006 with Changes No. 1 and No. 2. Poland, Germany and Spain: the snow and wind values of the national annex at the nearest main city, combined by EN 1990 with the factor 1.5 on snow and wind, with the canopy coefficients of EN 1991-1-3 and EN 1991-1-4. The methodology page lists the rest.

Why can a maker’s configurator give less ballast?

A maker can use a wind-tunnel report for its own system, which allows a shelter factor for rows behind rows and for deflectors. EN 1991-1-4 gives no such reduction, and Solispec does not model it, so each row is an isolated canopy. Check the maker’s approval if you rely on its system.

Does a matching result mean the design is approved?

No. It shows that the arithmetic and the coefficients are applied as stated. The result is preliminary; a qualified engineer must verify it for the site, the roof or the soil, and the local rules.