10 kWp ground mount: the engine against a hand calculation

A typical 10.44 kWp ground-mount structure near Lublin calculated twice, by the Solispec engine and by hand, step by step. Snow, wind, purlin, rafter, footing, bolt and a table of differences.

By Solispec editorial11 min read

A ground mount near Lublin is 18 modules of 580 W (10.44 kWp) in two rows, 30 degrees, 6 frames at 1980 mm. The C 60 x 40 x 2 purlin is the most loaded (79 %). Engine and hand calculation differ under 1 %, except on the continuous beam, where the engine is cautious. The calculation is preliminary.

An installer is right not to trust an automated structural result until someone has checked it, and a methodology page will not change that. So one typical case is calculated twice here: by the engine and on paper, with the formulas and inputs written out. The comparison table is below, and the differences are explained plainly. Three other cases with a shorter write-up are on the calculation check page.

The structure

  • Site: near Lublin, Solispec city data for Lublin (snow zone 3, wind zone 1, 184 m above sea level), terrain category II.
  • Module: LONGi Hi-MO 6 LR5-72HTH-580M, 580 W, 2278 x 1134 mm. 2 rows of 9 modules in portrait: 18 modules, 10.44 kWp.
  • Tilt 30 degrees, lower edge 800 mm above ground, upper edge 3118 mm. The slope is 4576 mm long, the table is 10366 mm long.
  • 6 frames at 1980 mm, 12 posts in all. Purlins: C 60 x 40 x 2, 2 per module row (4 lines), 510 mm from the module end. Rafter: C 100 x 50 x 2.5. Posts: tube 60 x 60 x 2.
  • Footing under each post: concrete Ø350 mm, 1300 mm deep, 0.125 m³ per post.

The layout is typical: at the default frame spacing of 2000 mm the engine tightens the frames to 1980 mm to divide the table evenly. At a spacing of 2440 mm the same purlin would give 120 % and the engine would mark it critical.

Snow and wind for Lublin

Values per the national annex from the Solispec city data. Lublin is on the city list of the snow and wind calculator and gives the same figures there.

Value
Snow zone / wind zone3 / 1
Altitude, m184
s_k, Pa (PN-EN 1991-1-3 + NA)1200
q_b, Pa (PN-EN 1991-1-4 + NA)300

In zone 3 s_k = max(1.2; 0.006 A − 0.6) kN/m², and at 184 m the minimum 1.2 governs, since 0.006 · 184 − 0.6 = 0.50. In wind zone 1 q_b = 0.30 kN/m².

Hand calculation: loads

Design values use γ_Q = 1.5 for snow and wind (EN 1990, table A1.2(B)).

Snow. For a slope up to 30 degrees the shape coefficient is μ = 0.8 (EN 1991-1-3, table 5.2), C_e = C_t = 1.

  • On the horizontal projection: S = 1.5 · 0.8 · 1200 = 1440 Pa.
  • Perpendicular to the module: S · cos² 30° = 1440 · 0.75 = 1080 Pa.

Wind. Pressure centre at z = 3.1 m (top of the table), terrain II: z₀ = 0.05 m, k_r = 0.19 (EN 1991-1-4, 4.3 and 4.5).

  • Turbulence intensity: I_v = 1 / ln(z / z₀) = 1 / ln(62) = 0.242.
  • c_r = k_r · ln(z / z₀) = 0.19 · 4.127 = 0.784.
  • c_e(z) = (1 + 7 · I_v) · c_r² = 2.696 · 0.6149 = 1.658.
  • W = 1.5 · c_e · q_b = 1.5 · 1.658 · 300 = 746 Pa.
  • Canopy force coefficients for φ = 0 at 30 degrees (EN 1991-1-4, table 7.6): suction 1.80, pressure 1.20. Downward wind on the module: 746 · 1.20 = 895 Pa.

Dead load. The engine takes 120 Pa for module and rail. We use the same by hand.

Hand calculation: the purlin (governing member)

The load strip of one purlin is half the module length: b = 2278 / 2 = 1139 mm. Two combinations per EN 1990 (6.10), ψ₀ = 0.6 for wind and 0.5 for snow:

  • snow leading: 1.35 · 120 + 1080 + 0.6 · 895 = 1779 Pa;
  • wind leading: 1.35 · 120 + 895 + 0.5 · 1080 = 1597 Pa.

The first governs. Line load: q_d = 1779 Pa · 1139 mm · 10⁻⁶ = 2.026 N/mm.

At span L = 1980 mm, as a simply supported beam (the way the engine does it):

  • M = q_d · L² / 8 = 2.026 · 1980² / 8 = 0.993 kNm;
  • section modulus (effective section of C 60 x 40 x 2 from the engine catalog) W = 5350 mm³, f_y = 235 MPa;
  • utilisation: M / (W · f_y) = 993 000 / (5350 · 235) = 0.790, i.e. 79 %.

Deflection uses characteristic values, G + S + 0.6 · W (EN 1990 (6.14b)): (120 + 1080 / 1.5 + 0.6 · 895 / 1.5) Pa = 1198 Pa, so q_k = 1.365 N/mm. For E = 210 000 MPa and I = 160 000 mm⁴:

  • simply supported: 5 · q_k · L⁴ / (384 · E · I) = 8.13 mm, which is 0.82 of the L/200 limit of 9.9 mm;
  • the engine multiplies this by 0.6 because the purlin has 5 spans: 4.88 mm, i.e. 49 % of the limit.

Hand calculation: rafter and footing

Rafter C 100 x 50 x 2.5. Load from the purlins onto the frame: q = 1779 Pa · 1980 mm · 10⁻⁶ = 3.523 N/mm along the slope. The geometry is taken from the engine: 2178 mm between the posts, cantilevers of 789 mm. The moment is the larger of q · L² / 8 − q · (2 · 789²) / 4 = 0.99 kNm and q · 789² / 2 = 1.10 kNm. Utilisation: 1 096 000 / (15 500 · 235) = 30 %.

Footing uplift. Module area per frame: A = 4.576 m · 1.98 m = 9.06 m². Vertical wind force: F_z = c_f(suction) · W · A · cos α = 1.80 · 746 · 9.06 · 0.866 = 10.54 kN. The front post takes 0.75 · F_z = 7.90 kN.

Holding force of a Ø350 x 1300 footing: concrete volume π · 0.175² · 1.3 = 0.125 m³, weight 0.9 · 0.125 · 24 kN/m³ = 2.70 kN, soil friction on the side 15 kPa · π · 0.35 · 1.3 · 0.5 = 10.72 kN (the factor 0.5 is an assumption of the engine). Total 13.42 kN, utilisation 7.90 / 13.42 = 59 %. Footing depth 1.30 m against frost depth 1.20 m (map PN-81/B-03020, zone III, an indicative value).

Hand calculation: one connection

The purlin-to-rafter connection is one M10 grade 8.8 bolt per crossing (24 bolts M10 x 140 for 6 frames and 4 purlins). In this mode the engine lists the bolts in the bill of materials but does not report their utilisation, so this one is a hand calculation only. The resistance formulas (EN 1993-1-8 and EN 1993-1-3, table 8.4) are the ones the engine uses in its other bolt checks.

Loaded area of one crossing: 1.139 m · 1.98 m = 2.255 m². The reaction at the first interior support of a five-span beam is 1.13 · q · L instead of 0.5 · q · L, hence the factor 1.13.

  • Shear along the slope from snow and dead load: (1.35 · 120 · sin 30° + 1440 · cos 30° · sin 30°) · 2.255 · 1.13 = 1.80 kN.
  • Shear resistance: F_v,Rd = 0.6 · 800 · 58 / 1.25 = 22.27 kN.
  • Bearing on the 2 mm wall: F_b,Rd = 2.5 · α_b · k_t · f_u · d · t / γ_M2 = 2.5 · 1 · 1 · 360 · 10 · 2 / 1.25 = 14.40 kN (α_b = 1 at an edge distance of at least 30 mm, k_t = 1 for t > 1.25 mm, f_u = 360 MPa).
  • Utilisation: 1.80 / 14.40 = 12.5 %.
  • Tension from wind suction: (1.80 · 746 − 0.9 · 120 · cos 30°) · 2.255 · 1.13 = 3.18 kN, against F_t,Rd = 0.9 · 800 · 58 / 1.25 = 33.4 kN and wall punching B_p,Rd = 21.7 kN. Utilisation 15 %.

Engine against hand calculation

The difference is (engine − hand) / hand. The engine values are as the report prints them, so part of the difference is rounding.

QuantityEngineHandDifference
Snow on the projection S, Pa144014400.0 %
Snow perpendicular to the module, Pa108010800.0 %
c_e(z)1.661.658+0.1 %
Wind W, Pa747746+0.1 %
Purlin, q_d, N/mm2.0282.026+0.1 %
Purlin, moment M, kNm0.990.993−0.3 %
Purlin, strength utilisation79 %79.0 %0.0 %
Purlin, deflection against L/20049 %49.3 %−0.6 %
Rafter, moment, kNm1.101.096+0.4 %
Rafter, utilisation30 %30.1 %−0.3 %
Footing, uplift, kN7.927.90+0.3 %
Footing, holding force, kN13.4213.420.0 %
Footing, utilisation59 %58.9 %+0.2 %
M10 bolt, utilisationnot reported12.5 %no comparison

Where the differences come from

  • Rounding. By hand we took z = 3.1 m, while the engine uses the exact top height of the table, 3.118 m, and prints results with 2 to 3 digits. Hence 0.1 % to 0.6 % in the table. This is not an error, only a difference in notation.
  • Continuous beam. This is the only difference that matters. The purlin has 5 spans. A moment calculated as for a simply supported beam, q · L² / 8, is the coefficient 0.125. For five equal spans under full load the support moment is 0.105 · q · L², i.e. 0.84 kNm and 66 % instead of 0.99 kNm and 79 %. The deflection of the end span is 0.00657 · q_k · L⁴ / (E · I) = 4.10 mm, i.e. 41 % instead of 49 % (the engine multiplies the simply supported deflection by 0.6, while the calculation gives 0.50). So the engine is about 19 % more cautious. The assumption is deliberate: snow can lie on only some of the spans, and a load arrangement unfavourable to a continuous beam gives larger moments than full load. Under either assumption the purlin passes.
  • Dead load. A flat 120 Pa for module and rail is the engine's approximation, and we use the same by hand. Every extra 10 Pa of dead load raises the purlin utilisation by about 0.6 percentage points. The real weight of the module and rail is entered in the inputs.
  • Section data. The section modulus W = 5350 mm³ and moment of inertia I = 160 000 mm⁴ are the engine's catalog values, not ours. We did not derive them by hand, so the agreement in the table does not check the sections themselves. The effective section of a thin-walled C profile depends on the manufacturer and the batch, and the engineer should confirm it from the manufacturer's data sheet.
  • The same formulas. This is deliberate: we check that the engine has no error in inputs, combinations and arithmetic, not whether the standards are good. An independent engineering verification is only planned.

No difference points to an engine error. The largest, about 19 % in the purlin, comes from a stated simplification and is on the safe side.

Steel list from the engine

ItemSectionQuantity x cut length
Front posttube 60 x 60 x 26 x 2629 mm (1300 mm in concrete)
Rear posttube 60 x 60 x 26 x 3718 mm
RafterC 100 x 50 x 2.56 x 3756 mm
Knee braceC 60 x 40 x 26 x 1906 mm
Cross brace between rear postsC 60 x 40 x 24 x 2655 mm
PurlinsC 60 x 40 x 24 lines from pieces of 6000 mm and 4506 mm, 4 connectors

In all 124.7 m of profile from 27 sticks of 6000 mm and 1.65 m³ of concrete with a 10 % margin. M10 bolts: 24 x M10 x 150 (post to rafter), 24 x M10 x 140 (purlin to rafter), 6 x M10 x 100, 6 x M10 x 160 and 8 x M10 x 180 through spacer inserts, 18 x M10 x 25. The modules are held by 8 end clamps and 32 mid clamps. The M10 bolts are grade 8.8.

What the result is

For a typical 10 kWp ground-mount structure near Lublin, the engine and the hand calculation agree within 1 % where they calculate the same way, and where they calculate differently the engine is the more cautious. That is a good result, but not proof of correctness for every site. The engine's result is a preliminary design: a qualified structural engineer who knows the ground, the frost zone and the local rules checks it before installation. It still gives the installer numbers that can be traced, not a black box.

Have your own site and want to see how the engine calculates it? Send us your object: we check it the same way and compare it with a hand calculation. The ground layout is described under ground mounting, and a sample report with drawings and the cutting list is on the samples page. You can calculate your own structure in the Solispec designer.

This is a preliminary calculation; a qualified structural engineer checks it before installation. Loads are values entered per the national annex, design values per EN 1990.

FAQ

Can the engine result be trusted without a hand calculation?

Not without a check. In this article the same inputs are calculated on paper and by the engine. The differences in loads, moment and utilisation are under 1 %, and on the continuous beam the engine is about 19 % more cautious. The result is still preliminary and a qualified structural engineer checks it.

Which member governs a 10 kWp ground mount near Lublin?

The C 60 x 40 x 2 purlin at a frame spacing of 1980 mm: 79 % of strength and 49 % of the L/200 deflection limit. At a spacing of 2440 mm the same purlin fails on strength (120 %).

What snow and wind should I use for Lublin?

Snow zone 3, s_k = 1200 Pa, wind zone 1, q_b = 300 Pa. These are values per the national annex for the city, so check the zone of the actual plot on the annex map, especially near a zone boundary.

StructuresNorms

News and design tips

What’s new in Solispec, changes to the standards and practical tips on designing solar power systems.

What interests you

How we handle your data: privacy policy.

Ground frame designer

Design the ground frame for your solar plant

Solispec picks the profiles and posts, checks the frame against snow and wind to the DBN and prices it down to the last bolt.

  • No sign-up
  • Snow and wind check
  • Drawings and estimate