Glossary · Steel structures
Buckling reduction factor φ (χ)
A factor that reduces a compressed member’s resistance for flexural buckling: φ in DBN V.2.6-198, χ in Eurocode 3.
Ground frame designer
Design the ground frame for your solar plant
Solispec picks the profiles and posts, checks the frame against snow and wind to the DBN and prices it down to the last bolt.
- No sign-up
- Snow and wind check
- Drawings and estimate
Definition
A long compressed member — a truss leg or brace — buckles before its stresses reach yield. So its resistance is multiplied by a factor below one that depends on the relative slenderness λ̄ (length, section and steel).
For tubes under DBN V.2.6-198:2014 the factor φ comes from formulas (8.4)–(8.5). Solispec puts a closed bent-and-welded tube on curve b (α = 0.04, β = 0.09, Table 8.1):
φ = 0,5/λ̄² · (δ − √(δ² − 39,48 · λ̄²)), δ = 9,87 · (1 − α + β · λ̄) + λ̄²At λ̄ ≤ 0.4, φ = 1, so a short member works at full strength; for curve b at λ̄ > 4.4, φ is at most 7.6/λ̄². For compression with bending the DBN gives a separate factor φe from Table Ж.3.
For a C-profile the same idea is χ under EN 1993-1-1:2005 (cl. 6.3.1.2, eq. 6.49), with curve b (α = 0.34, Table 6.1), but computed for the effective section. The simplest way to reduce slenderness is a shorter free length: an extra brace or tie.
How this applies to a PV truss. The compressed members of a ground truss are the legs and braces under snow, and under wind from below some members change the sign of their force. The buckling lengths in and out of the truss plane differ, since trusses are tied to each other only by the rails, so the engine checks both. An extra brace or tie shortens the free length, which directly raises φ. The Solispec constructor shows each member's utilisation and the governing check, so you can see where the truss lacks stability.
How Solispec applies it
The Solispec engine computes φ and φe for every tube member of the truss (phiDbn, phiE) with in-plane and out-of-plane lengths. For the C-profile it computes χ per EN 1993-1-1:2005 on the effective section, for flexural, torsional and flexural-torsional modes, and shows each member’s utilisation in the report.
Norms and clauses
- DBN V.2.6-198:2014, eq. (8.4)–(8.5), Table 8.1, Table Ж.3
- EN 1993-1-1:2005, cl. 6.3.1.2, Table 6.1
Related terms
- Thin-walled cold-formed C-profileA bent steel section with thin walls that buckles locally before yielding; it is designed to DSTU-N B EN 1993-1-3:2012.
- Effective cross-sectionThe part of a thin-walled section that still carries compression after its walls buckle locally; computed per EN 1993-1-5 and EN 1993-1-3.
- Steel partial factors γM and γmFactors that divide the characteristic steel resistance: γ_M per Eurocode for C-profiles, γ_m per DBN V.2.6-198 for tubes.
- DBN V.2.6-198:2014 “Steel structures”: tubes in PV framesNorms explained
- DSTU-N B EN 1993-1-3:2012: designing C-profiles for PV mountingNorms explained