Astronergy ASTRO N5 CHSM72N(DG)/F-BH-590 + Deye SUN-5K-G05P1-EU-AM2: how many panels per string
From 2 to 8 Astronergy ASTRO N5 CHSM72N(DG)/F-BH-590 panels per string on an MPPT input of the Deye SUN-5K-G05P1-EU-AM2 inverter — in any climatic region of Ukraine. Below: the window for each region, the input currents and example plants laid out by the Solispec engine.
- Panels per string
- 2–8pcs
- Input V_max
- 550V
- MPPT window
- 70–500V
- Panel I_sc
- 14.13A
- MPPT input I_sc
- 27.0A
- Panel V_mp in heat
- 37.5V
Ground frame designer
A ground plant with Astronergy ASTRO N5 CHSM72N(DG)/F-BH-590
The builder opens with this panel and the Deye SUN-5K-G05P1-EU-AM2 inverter: Solispec lays out the strings itself.
- No sign-up
- Snow and wind check
- Drawings and estimate
String by climatic region
T_min per ДСТУ-Н Б В.1.1-27:2010, табл. 1; open-circuit voltage at T_min: K_U = 1 + α·(T_min − 25)/100 = 1.17 (α -0.25 %/K, T_min -42 °C; Annex B).
| Region | T_min | Panel U_oc at T_min, V | Min per string | Max per string | String U_oc at max, V (≤ 550) |
|---|---|---|---|---|---|
| Region I | -40 °C | 61.17 | 2 | 8 | 489.4 |
| Region II | -42 °C | 61.43 | 2 | 8 | 491.5 |
| Region IIIA | -38 °C | 60.91 | 2 | 9 | 548.2 |
| Region IIIB | -32 °C | 60.12 | 2 | 9 | 541.1 |
| Region IV | -20 °C | 58.54 | 2 | 9 | 526.9 |
| Region V | -27 °C | 59.46 | 2 | 9 | 535.2 |
The minimum per string keeps the string voltage in heat (panel V_mp 37.5 V) above the MPPT window (70 V).
Input currents
| Panel I_sc / MPPT input I_sc, A | 14.13 / 27.0 |
|---|---|
| Panel I_mp / MPPT input I_mp, A | 13.40 / 18.0 |
| Parallel strings per MPPT | 1 |
| MPPT inputs | 2 |
No cautions about the currents.
Example plants
The Solispec engine laid out the strings for plants of several sizes with this inverter at the lowest T_min; only those that pass the checks with every panel placed are shown.
| Plant | Panels | kW DC | Inverters | Strings | DC/AC |
|---|---|---|---|---|---|
| ≈ 5 kW | 9 | 5.31 | 1 | 5 pan. × 1 — inv. 1, MPPT 1; 4 pan. × 1 — inv. 1, MPPT 2 | 1.06 |
| ≈ 10 kW | 17 | 10.03 | 2 | 5 pan. × 1 — inv. 1, MPPT 1; 5 pan. × 1 — inv. 1, MPPT 2; 5 pan. × 1 — inv. 2, MPPT 1; 2 pan. × 1 — inv. 2, MPPT 2 | 1.00 |
| ≈ 15 kW | 26 | 15.34 | 4 | 4 pan. × 1 — inv. 1, MPPT 1; 4 pan. × 1 — inv. 1, MPPT 2; 4 pan. × 1 — inv. 2, MPPT 1; 4 pan. × 1 — inv. 2, MPPT 2; 4 pan. × 1 — inv. 3, MPPT 1; 2 pan. × 1 — inv. 3, MPPT 2; 4 pan. × 1 — inv. 4, MPPT 1 | 0.77 |
- DC/AC 0.47 — inverter oversized
A preliminary calculation; a design needs an engineer's check. Solispec engine 0.12.0.