Risen RSM96-11-465BNDG + Deye SUN-5K-G05P1-EU-AM2: how many panels per string
From 3 to 13 Risen RSM96-11-465BNDG panels per string on an MPPT input of the Deye SUN-5K-G05P1-EU-AM2 inverter — in any climatic region of Ukraine. Below: the window for each region, the input currents and example plants laid out by the Solispec engine.
- Panels per string
- 3–13pcs
- Input V_max
- 550V
- MPPT window
- 70–500V
- Panel I_sc
- 16.38A
- MPPT input I_sc
- 27.0A
- Panel V_mp in heat
- 25.9V
Ground frame designer
A ground plant with Risen RSM96-11-465BNDG
The builder opens with this panel and the Deye SUN-5K-G05P1-EU-AM2 inverter: Solispec lays out the strings itself.
- No sign-up
- Snow and wind check
- Drawings and estimate
String by climatic region
T_min per ДСТУ-Н Б В.1.1-27:2010, табл. 1; open-circuit voltage at T_min: K_U = 1 + α·(T_min − 25)/100 = 1.17 (α -0.25 %/K, T_min -42 °C; Annex B).
| Region | T_min | Panel U_oc at T_min, V | Min per string | Max per string | String U_oc at max, V (≤ 550) |
|---|---|---|---|---|---|
| Region I | -40 °C | 41.85 | 3 | 13 | 544.1 |
| Region II | -42 °C | 42.03 | 3 | 13 | 546.4 |
| Region IIIA | -38 °C | 41.67 | 3 | 13 | 541.7 |
| Region IIIB | -32 °C | 41.13 | 3 | 13 | 534.7 |
| Region IV | -20 °C | 40.05 | 3 | 13 | 520.7 |
| Region V | -27 °C | 40.68 | 3 | 13 | 528.8 |
The minimum per string keeps the string voltage in heat (panel V_mp 25.9 V) above the MPPT window (70 V).
Input currents
| Panel I_sc / MPPT input I_sc, A | 16.38 / 27.0 |
|---|---|
| Panel I_mp / MPPT input I_mp, A | 15.30 / 18.0 |
| Parallel strings per MPPT | 1 |
| MPPT inputs | 2 |
No cautions about the currents.
Example plants
The Solispec engine laid out the strings for plants of several sizes with this inverter at the lowest T_min; only those that pass the checks with every panel placed are shown.
| Plant | Panels | kW DC | Inverters | Strings | DC/AC |
|---|---|---|---|---|---|
| ≈ 5 kW | 11 | 5.12 | 1 | 11 pan. × 1 — inv. 1, MPPT 1 | 1.02 |
| ≈ 10 kW | 22 | 10.23 | 2 | 11 pan. × 1 — inv. 1, MPPT 1; 11 pan. × 1 — inv. 2, MPPT 1 | 1.02 |
| ≈ 15 kW | 33 | 15.35 | 3 | 11 pan. × 1 — inv. 1, MPPT 1; 11 pan. × 1 — inv. 2, MPPT 1; 11 pan. × 1 — inv. 3, MPPT 1 | 1.02 |
A preliminary calculation; a design needs an engineer's check. Solispec engine 0.12.0.