Astronergy ASTRO N5 CHSM54N-HC-435 + Growatt SPF 5000 ES: how many panels per string

From 5 to 9 Astronergy ASTRO N5 CHSM54N-HC-435 panels per string on an MPPT input of the Growatt SPF 5000 ES inverter — in any climatic region of Ukraine. Below: the window for each region, the input currents and example plants laid out by the Solispec engine.

Panels per string
5–9pcs
Input V_max
450V
MPPT window
120–430V
Panel I_sc
14.19A
MPPT input I_sc
22.0A
Panel V_mp in heat
27.6V

Ground frame designer

A ground plant with Astronergy ASTRO N5 CHSM54N-HC-435

The builder opens with this panel and the Growatt SPF 5000 ES inverter: Solispec lays out the strings itself.

  • No sign-up
  • Snow and wind check
  • Drawings and estimate

String by climatic region

T_min per ДСТУ-Н Б В.1.1-27:2010, табл. 1; open-circuit voltage at T_min: K_U = 1 + α·(T_min − 25)/100 = 1.17 (α -0.25 %/K, T_min -42 °C; Annex B).

RegionT_minPanel U_oc at T_min, VMin per stringMax per stringString U_oc at max, V (≤ 450)
Region I-40 °C44.87510448.7
Region II-42 °C45.0759405.6
Region IIIA-38 °C44.68510446.8
Region IIIB-32 °C44.10510441.0
Region IV-20 °C42.94510429.4
Region V-27 °C43.62510436.2

The minimum per string keeps the string voltage in heat (panel V_mp 27.6 V) above the MPPT window (120 V).

Input currents

Panel I_sc / MPPT input I_sc, A14.19 / 22.0
Panel I_mp / MPPT input I_mp, A13.41 / 22.0
Parallel strings per MPPT1
MPPT inputs1

No cautions about the currents.

Example plants

The Solispec engine laid out the strings for plants of several sizes with this inverter at the lowest T_min; only those that pass the checks with every panel placed are shown.

PlantPanelskW DCInvertersStringsDC/AC
≈ 5 kW125.2226 pan. × 1 — inv. 1, MPPT 1; 6 pan. × 1 — inv. 2, MPPT 10.52
≈ 10 kW2310.0138 pan. × 1 — inv. 1, MPPT 1; 8 pan. × 1 — inv. 2, MPPT 1; 7 pan. × 1 — inv. 3, MPPT 10.67
≈ 15 kW3515.2349 pan. × 1 — inv. 1, MPPT 1; 9 pan. × 1 — inv. 2, MPPT 1; 9 pan. × 1 — inv. 3, MPPT 1; 8 pan. × 1 — inv. 4, MPPT 10.76
  • DC/AC 0.52 — inverter oversized
  • DC/AC 0.70 — inverter oversized
  • DC/AC 0.61 — inverter oversized

A preliminary calculation; a design needs an engineer's check. Solispec engine 0.12.0.