LONGi · Deye

LONGi Hi-MO X10 LR7-72HVH-650M + Deye SUN-10K-G06P3-EU-BM2: how many panels per string

From 4 to 17 LONGi Hi-MO X10 LR7-72HVH-650M panels per string on an MPPT input of the Deye SUN-10K-G06P3-EU-BM2 inverter — in any climatic region of Ukraine. Below: the window for each region, the input currents and example plants laid out by the Solispec engine.

Panels per string
4–17pcs
Input V_max
1,100V
MPPT window
120–1,000V
Panel I_sc
15.29A
MPPT input I_sc
19.5A
Panel V_mp in heat
37.9V

Ground frame designer

A ground plant with LONGi Hi-MO X10 LR7-72HVH-650M

The builder opens with this panel and the Deye SUN-10K-G06P3-EU-BM2 inverter: Solispec lays out the strings itself.

  • No sign-up
  • Snow and wind check
  • Drawings and estimate

String by climatic region

T_min per ДСТУ-Н Б В.1.1-27:2010, табл. 1; open-circuit voltage at T_min: K_U = 1 + α·(T_min − 25)/100 = 1.13 (α -0.2 %/K, T_min -42 °C; Annex B).

RegionT_minPanel U_oc at T_min, VMin per stringMax per stringString U_oc at max, V (≤ 1,100)
Region I-40 °C60.914181,096.3
Region II-42 °C61.124171,039.1
Region IIIA-38 °C60.694181,092.5
Region IIIB-32 °C60.044181,080.8
Region IV-20 °C58.754181,057.5
Region V-27 °C59.514181,071.1

The minimum per string keeps the string voltage in heat (panel V_mp 37.9 V) above the MPPT window (120 V).

Input currents

Panel I_sc / MPPT input I_sc, A15.29 / 19.5
Panel I_mp / MPPT input I_mp, A14.59 / 13.0
Parallel strings per MPPT1
MPPT inputs2
  • Power clippingThe panel's working current (14.59 A) is above the input's working current (13.0 A): on clear days the inverter clips part of the power.

Example plants

The Solispec engine laid out the strings for plants of several sizes with this inverter at the lowest T_min; only those that pass the checks with every panel placed are shown.

PlantPanelskW DCInvertersStringsDC/AC
≈ 5 kW85.2018 pan. × 1 — inv. 1, MPPT 10.52
≈ 10 kW1610.40116 pan. × 1 — inv. 1, MPPT 11.04
≈ 15 kW2415.60212 pan. × 1 — inv. 1, MPPT 1; 12 pan. × 1 — inv. 2, MPPT 10.78
  • current 14.6 A > 13 A — the inverter will clip (clipping)
  • DC/AC 0.52 — inverter oversized

A preliminary calculation; a design needs an engineer's check. Solispec engine 0.12.0.