LONGi · Deye
LONGi Hi-MO 9 LR7-72HYD-640M + Deye SUN-50K-G04: how many panels per string
From 6 to 18 LONGi Hi-MO 9 LR7-72HYD-640M panels per string on an MPPT input of the Deye SUN-50K-G04 inverter — in any climatic region of Ukraine. Below: the window for each region, the input currents and example plants laid out by the Solispec engine.
- Panels per string
- 6–18pcs
- Input V_max
- 1,100V
- MPPT window
- 200–1,000V
- Panel I_sc
- 15.09A
- MPPT input I_sc
- 60.0A
- Panel V_mp in heat
- 37.9V
Ground frame designer
A ground plant with LONGi Hi-MO 9 LR7-72HYD-640M
The builder opens with this panel and the Deye SUN-50K-G04 inverter: Solispec lays out the strings itself.
- No sign-up
- Snow and wind check
- Drawings and estimate
String by climatic region
T_min per ДСТУ-Н Б В.1.1-27:2010, табл. 1; open-circuit voltage at T_min: K_U = 1 + α·(T_min − 25)/100 = 1.13 (α -0.2 %/K, T_min -42 °C; Annex B).
| Region | T_min | Panel U_oc at T_min, V | Min per string | Max per string | String U_oc at max, V (≤ 1,100) |
|---|---|---|---|---|---|
| Region I | -40 °C | 60.57 | 6 | 18 | 1,090.2 |
| Region II | -42 °C | 60.78 | 6 | 18 | 1,094.1 |
| Region IIIA | -38 °C | 60.35 | 6 | 18 | 1,086.4 |
| Region IIIB | -32 °C | 59.71 | 6 | 18 | 1,074.8 |
| Region IV | -20 °C | 58.42 | 6 | 18 | 1,051.6 |
| Region V | -27 °C | 59.17 | 6 | 18 | 1,065.1 |
The minimum per string keeps the string voltage in heat (panel V_mp 37.9 V) above the MPPT window (200 V).
Input currents
| Panel I_sc / MPPT input I_sc, A | 15.09 / 60.0 |
|---|---|
| Panel I_mp / MPPT input I_mp, A | 14.40 / 40.0 |
| Parallel strings per MPPT | 2 |
| MPPT inputs | 4 |
No cautions about the currents.
Example plants
The Solispec engine laid out the strings for plants of several sizes with this inverter at the lowest T_min; only those that pass the checks with every panel placed are shown.
| Plant | Panels | kW DC | Inverters | Strings | DC/AC |
|---|---|---|---|---|---|
| ≈ 5 kW | 8 | 5.12 | 1 | 8 pan. × 1 — inv. 1, MPPT 1 | 0.10 |
| ≈ 10 kW | 16 | 10.24 | 1 | 16 pan. × 1 — inv. 1, MPPT 1 | 0.20 |
| ≈ 15 kW | 24 | 15.36 | 1 | 12 pan. × 2 — inv. 1, MPPT 1 | 0.31 |
- DC/AC 0.10 — inverter oversized
- DC/AC 0.20 — inverter oversized
- DC/AC 0.31 — inverter oversized
A preliminary calculation; a design needs an engineer's check. Solispec engine 0.12.0.