Jinko · Deye
Jinko Tiger Neo JKM640N-78HL4-BDV + Deye SUN-20K-SG01HP3-EU-AM2: how many panels per string
From 4 to 14 Jinko Tiger Neo JKM640N-78HL4-BDV panels per string on an MPPT input of the Deye SUN-20K-SG01HP3-EU-AM2 inverter — in any climatic region of Ukraine. Below: the window for each region, the input currents and example plants laid out by the Solispec engine.
- Panels per string
- 4–14pcs
- Input V_max
- 1,000V
- MPPT window
- 150–850V
- Panel I_sc
- 13.98A
- MPPT input I_sc
- 39.0A
- Panel V_mp in heat
- 40.9V
Ground frame designer
A ground plant with Jinko Tiger Neo JKM640N-78HL4-BDV
The builder opens with this panel and the Deye SUN-20K-SG01HP3-EU-AM2 inverter: Solispec lays out the strings itself.
- No sign-up
- Snow and wind check
- Drawings and estimate
String by climatic region
T_min per ДСТУ-Н Б В.1.1-27:2010, табл. 1; open-circuit voltage at T_min: K_U = 1 + α·(T_min − 25)/100 = 1.17 (α -0.25 %/K, T_min -42 °C; Annex B).
| Region | T_min | Panel U_oc at T_min, V | Min per string | Max per string | String U_oc at max, V (≤ 1,000) |
|---|---|---|---|---|---|
| Region I | -40 °C | 66.66 | 4 | 15 | 999.9 |
| Region II | -42 °C | 66.94 | 4 | 14 | 937.2 |
| Region IIIA | -38 °C | 66.37 | 4 | 15 | 995.6 |
| Region IIIB | -32 °C | 65.51 | 4 | 15 | 982.7 |
| Region IV | -20 °C | 63.79 | 4 | 15 | 956.9 |
| Region V | -27 °C | 64.79 | 4 | 15 | 971.9 |
The minimum per string keeps the string voltage in heat (panel V_mp 40.9 V) above the MPPT window (150 V).
Input currents
| Panel I_sc / MPPT input I_sc, A | 13.98 / 39.0 |
|---|---|
| Panel I_mp / MPPT input I_mp, A | 13.33 / 26.0 |
| Parallel strings per MPPT | 1 |
| MPPT inputs | 2 |
No cautions about the currents.
Example plants
The Solispec engine laid out the strings for plants of several sizes with this inverter at the lowest T_min; only those that pass the checks with every panel placed are shown.
| Plant | Panels | kW DC | Inverters | Strings | DC/AC |
|---|---|---|---|---|---|
| ≈ 5 kW | 8 | 5.12 | 1 | 8 pan. × 1 — inv. 1, MPPT 1 | 0.26 |
| ≈ 10 kW | 16 | 10.24 | 1 | 8 pan. × 1 — inv. 1, MPPT 1; 8 pan. × 1 — inv. 1, MPPT 2 | 0.51 |
| ≈ 15 kW | 24 | 15.36 | 1 | 12 pan. × 1 — inv. 1, MPPT 1; 12 pan. × 1 — inv. 1, MPPT 2 | 0.77 |
- DC/AC 0.26 — inverter oversized
- DC/AC 0.51 — inverter oversized
A preliminary calculation; a design needs an engineer's check. Solispec engine 0.12.0.