Jinko · Deye
Jinko Tiger Neo JKM440N-54HL4R-BDV + Deye SUN-10K-SG02LP1-EU-AM3: how many panels per string
From 6 to 10 Jinko Tiger Neo JKM440N-54HL4R-BDV panels per string on an MPPT input of the Deye SUN-10K-SG02LP1-EU-AM3 inverter — in any climatic region of Ukraine. Below: the window for each region, the input currents and example plants laid out by the Solispec engine.
- Panels per string
- 6–10pcs
- Input V_max
- 500V
- MPPT window
- 150–425V
- Panel I_sc
- 14.35A
- MPPT input I_sc
- 44.0A
- Panel V_mp in heat
- 27.6V
Ground frame designer
A ground plant with Jinko Tiger Neo JKM440N-54HL4R-BDV
The builder opens with this panel and the Deye SUN-10K-SG02LP1-EU-AM3 inverter: Solispec lays out the strings itself.
- No sign-up
- Snow and wind check
- Drawings and estimate
String by climatic region
T_min per ДСТУ-Н Б В.1.1-27:2010, табл. 1; open-circuit voltage at T_min: K_U = 1 + α·(T_min − 25)/100 = 1.17 (α -0.25 %/K, T_min -42 °C; Annex B).
| Region | T_min | Panel U_oc at T_min, V | Min per string | Max per string | String U_oc at max, V (≤ 500) |
|---|---|---|---|---|---|
| Region I | -40 °C | 45.31 | 6 | 11 | 498.5 |
| Region II | -42 °C | 45.51 | 6 | 10 | 455.1 |
| Region IIIA | -38 °C | 45.12 | 6 | 11 | 496.3 |
| Region IIIB | -32 °C | 44.53 | 6 | 11 | 489.9 |
| Region IV | -20 °C | 43.37 | 6 | 11 | 477.0 |
| Region V | -27 °C | 44.05 | 6 | 11 | 484.5 |
The minimum per string keeps the string voltage in heat (panel V_mp 27.6 V) above the MPPT window (150 V).
Input currents
| Panel I_sc / MPPT input I_sc, A | 14.35 / 44.0 |
|---|---|
| Panel I_mp / MPPT input I_mp, A | 13.58 / 26.0 |
| Parallel strings per MPPT | 1 |
| MPPT inputs | 3 |
No cautions about the currents.
Example plants
The Solispec engine laid out the strings for plants of several sizes with this inverter at the lowest T_min; only those that pass the checks with every panel placed are shown.
| Plant | Panels | kW DC | Inverters | Strings | DC/AC |
|---|---|---|---|---|---|
| ≈ 5 kW | 12 | 5.28 | 1 | 6 pan. × 1 — inv. 1, MPPT 1; 6 pan. × 1 — inv. 1, MPPT 2 | 0.53 |
| ≈ 10 kW | 23 | 10.12 | 1 | 8 pan. × 1 — inv. 1, MPPT 1; 8 pan. × 1 — inv. 1, MPPT 2; 7 pan. × 1 — inv. 1, MPPT 3 | 1.01 |
| ≈ 15 kW | 35 | 15.40 | 2 | 7 pan. × 1 — inv. 1, MPPT 1; 7 pan. × 1 — inv. 1, MPPT 2; 7 pan. × 1 — inv. 1, MPPT 3; 7 pan. × 1 — inv. 2, MPPT 1; 7 pan. × 1 — inv. 2, MPPT 2 | 0.77 |
- DC/AC 0.53 — inverter oversized
- DC/AC 0.62 — inverter oversized
A preliminary calculation; a design needs an engineer's check. Solispec engine 0.12.0.