JA Solar JAM54D41-450/LB + Deye SUN-50K-G04: how many panels per string

From 8 to 23 JA Solar JAM54D41-450/LB panels per string on an MPPT input of the Deye SUN-50K-G04 inverter — in any climatic region of Ukraine. Below: the window for each region, the input currents and example plants laid out by the Solispec engine.

Panels per string
8–23pcs
Input V_max
1,100V
MPPT window
200–1,000V
Panel I_sc
14.48A
MPPT input I_sc
60.0A
Panel V_mp in heat
28.0V

Ground frame designer

A ground plant with JA Solar JAM54D41-450/LB

The builder opens with this panel and the Deye SUN-50K-G04 inverter: Solispec lays out the strings itself.

  • No sign-up
  • Snow and wind check
  • Drawings and estimate

String by climatic region

T_min per ДСТУ-Н Б В.1.1-27:2010, табл. 1; open-circuit voltage at T_min: K_U = 1 + α·(T_min − 25)/100 = 1.17 (α -0.26 %/K, T_min -42 °C; Annex B).

RegionT_minPanel U_oc at T_min, VMin per stringMax per stringString U_oc at max, V (≤ 1,100)
Region I-40 °C45.948231,056.7
Region II-42 °C46.158231,061.4
Region IIIA-38 °C45.748241,097.7
Region IIIB-32 °C45.128241,083.0
Region IV-20 °C43.908251,097.5
Region V-27 °C44.618241,070.7

The minimum per string keeps the string voltage in heat (panel V_mp 28.0 V) above the MPPT window (200 V).

Input currents

Panel I_sc / MPPT input I_sc, A14.48 / 60.0
Panel I_mp / MPPT input I_mp, A13.71 / 40.0
Parallel strings per MPPT2
MPPT inputs4

No cautions about the currents.

Example plants

The Solispec engine laid out the strings for plants of several sizes with this inverter at the lowest T_min; only those that pass the checks with every panel placed are shown.

PlantPanelskW DCInvertersStringsDC/AC
≈ 5 kW125.40112 pan. × 1 — inv. 1, MPPT 10.11
≈ 10 kW2310.35123 pan. × 1 — inv. 1, MPPT 10.21
≈ 15 kW3415.30117 pan. × 2 — inv. 1, MPPT 10.31
  • DC/AC 0.11 — inverter oversized
  • U_OC MAX 1 061 В > 1000 В — звірте максимальну напругу системи панелей і апаратів (паспорт, 712.512.1.1)
  • DC/AC 0.21 — inverter oversized
  • DC/AC 0.31 — inverter oversized

A preliminary calculation; a design needs an engineer's check. Solispec engine 0.12.0.