Astronergy ASTRO N7s CHSM54RN(DG)/F-BH-520 + Solis S6-GR1P5K: how many panels per string
From 4 to 12 Astronergy ASTRO N7s CHSM54RN(DG)/F-BH-520 panels per string on an MPPT input of the Solis S6-GR1P5K inverter — in any climatic region of Ukraine. Below: the window for each region, the input currents and example plants laid out by the Solispec engine.
- Panels per string
- 4–12pcs
- Input V_max
- 600V
- MPPT window
- 90–520V
- Panel I_sc
- 15.82A
- MPPT input I_sc
- 22.0A
- Panel V_mp in heat
- 29.3V
Ground frame designer
A ground plant with Astronergy ASTRO N7s CHSM54RN(DG)/F-BH-520
The builder opens with this panel and the Solis S6-GR1P5K inverter: Solispec lays out the strings itself.
- No sign-up
- Snow and wind check
- Drawings and estimate
String by climatic region
T_min per ДСТУ-Н Б В.1.1-27:2010, табл. 1; open-circuit voltage at T_min: K_U = 1 + α·(T_min − 25)/100 = 1.17 (α -0.25 %/K, T_min -42 °C; Annex B).
| Region | T_min | Panel U_oc at T_min, V | Min per string | Max per string | String U_oc at max, V (≤ 600) |
|---|---|---|---|---|---|
| Region I | -40 °C | 48.12 | 4 | 12 | 577.4 |
| Region II | -42 °C | 48.32 | 4 | 12 | 579.9 |
| Region IIIA | -38 °C | 47.91 | 4 | 12 | 574.9 |
| Region IIIB | -32 °C | 47.29 | 4 | 12 | 567.5 |
| Region IV | -20 °C | 46.05 | 4 | 13 | 598.6 |
| Region V | -27 °C | 46.77 | 4 | 12 | 561.3 |
The minimum per string keeps the string voltage in heat (panel V_mp 29.3 V) above the MPPT window (90 V).
Input currents
| Panel I_sc / MPPT input I_sc, A | 15.82 / 22.0 |
|---|---|
| Panel I_mp / MPPT input I_mp, A | 15.10 / 14.0 |
| Parallel strings per MPPT | 1 |
| MPPT inputs | 2 |
- Power clippingThe panel's working current (15.10 A) is above the input's working current (14.0 A): on clear days the inverter clips part of the power.
Example plants
The Solispec engine laid out the strings for plants of several sizes with this inverter at the lowest T_min; only those that pass the checks with every panel placed are shown.
| Plant | Panels | kW DC | Inverters | Strings | DC/AC |
|---|---|---|---|---|---|
| ≈ 5 kW | 10 | 5.20 | 1 | 10 pan. × 1 — inv. 1, MPPT 1 | 1.04 |
| ≈ 10 kW | 20 | 10.40 | 2 | 10 pan. × 1 — inv. 1, MPPT 1; 10 pan. × 1 — inv. 2, MPPT 1 | 1.04 |
| ≈ 15 kW | 29 | 15.08 | 3 | 5 pan. × 1 — inv. 1, MPPT 1; 5 pan. × 1 — inv. 1, MPPT 2; 5 pan. × 1 — inv. 2, MPPT 1; 5 pan. × 1 — inv. 2, MPPT 2; 5 pan. × 1 — inv. 3, MPPT 1; 4 pan. × 1 — inv. 3, MPPT 2 | 1.01 |
- current 15.1 A > 14 A — the inverter will clip (clipping)
A preliminary calculation; a design needs an engineer's check. Solispec engine 0.12.0.