Astronergy · Kstar

Astronergy ASTRO N5 CHSM72N-HC-590 + Kstar BluE-10KT-M6: how many panels per string

From 4 to 18 Astronergy ASTRO N5 CHSM72N-HC-590 panels per string on an MPPT input of the Kstar BluE-10KT-M6 inverter — in any climatic region of Ukraine. Below: the window for each region, the input currents and example plants laid out by the Solispec engine.

Panels per string
4–18pcs
Input V_max
1,100V
MPPT window
140–1,000V
Panel I_sc
14.27A
MPPT input I_sc
30.0A
Panel V_mp in heat
36.9V

Ground frame designer

A ground plant with Astronergy ASTRO N5 CHSM72N-HC-590

The builder opens with this panel and the Kstar BluE-10KT-M6 inverter: Solispec lays out the strings itself.

  • No sign-up
  • Snow and wind check
  • Drawings and estimate

String by climatic region

T_min per ДСТУ-Н Б В.1.1-27:2010, табл. 1; open-circuit voltage at T_min: K_U = 1 + α·(T_min − 25)/100 = 1.17 (α -0.25 %/K, T_min -42 °C; Annex B).

RegionT_minPanel U_oc at T_min, VMin per stringMax per stringString U_oc at max, V (≤ 1,100)
Region I-40 °C60.714181,092.7
Region II-42 °C60.974181,097.4
Region IIIA-38 °C60.444181,088.0
Region IIIB-32 °C59.664181,073.9
Region IV-20 °C58.094181,045.7
Region V-27 °C59.014181,062.2

The minimum per string keeps the string voltage in heat (panel V_mp 36.9 V) above the MPPT window (140 V).

Input currents

Panel I_sc / MPPT input I_sc, A14.27 / 30.0
Panel I_mp / MPPT input I_mp, A13.61 / 20.0
Parallel strings per MPPT1
MPPT inputs2

No cautions about the currents.

Example plants

The Solispec engine laid out the strings for plants of several sizes with this inverter at the lowest T_min; only those that pass the checks with every panel placed are shown.

PlantPanelskW DCInvertersStringsDC/AC
≈ 5 kW95.3119 pan. × 1 — inv. 1, MPPT 10.53
≈ 10 kW1710.03117 pan. × 1 — inv. 1, MPPT 11.00
≈ 15 kW2615.34213 pan. × 1 — inv. 1, MPPT 1; 13 pan. × 1 — inv. 2, MPPT 10.77
  • DC/AC 0.53 — inverter oversized
  • U_OC MAX 1 036 В > 1000 В — звірте максимальну напругу системи панелей і апаратів (паспорт, 712.512.1.1)

A preliminary calculation; a design needs an engineer's check. Solispec engine 0.12.0.