Can the roof carry solar panels? A worked example, Lviv
A 35 degree pitched roof under metal tile in Lviv, 10 panels. Snow and wind per DBN V.1.2-2:2006, the force on each hook, the hook spacing, what the engine checks and what is left to an engineer: rafters, section, condition of the timber.
Ten tekst nie jest jeszcze przetłumaczony na Twój język — pokazujemy oryginał.
The mounting system for 10 panels (5.8 kWp) on a 35 degree metal-tile roof in Lviv passes in the Solispec engine: each of the 20 hooks takes about 1.86 kN uplift and 1.06 kN pressure. The panels add 3.10 kN. Whether the rafters carry it, the engine does not calculate. The calculation is preliminary.
The example is made up, but the numbers are real: the engine produces each of them, and the simple derived ones are recomputed in the article's test. This is how an installer evaluates a customer's roof before a quote: the mounting system on paper, the roof structure on site.
What roof and panel layout is this?
- A house in Lviv, gable roof at 35 degrees under metal tile. Roof length along the eave 10 m, slope length 6 m, ridge height 7 m, terrain category II, 300 m above sea level.
- Rafters at 900 mm. This is an assumption, to be measured on site.
- Module LONGi Hi-MO 6 LR5-72HTH-580M: 580 W, 2278 x 1134 x 30 mm. 10 modules in portrait, 2 rows of 5: 5.8 kWp, panel area 25.83 m², which is 43 % of the slope.
- Aluminium rails 40 x 40, 2 per row. Fixing: M10 x 200 lag screw with an L-bracket and EPDM into the rafters.
- Default setbacks: eave 400 mm, ridge 300 mm, gable 400 mm.
How much load do solar panels add to a roof?
The engine takes the permanent load as 120 Pa on the panel area (a panel with rails, about 12 kg per m²). On 25.83 m² that is 3.10 kN, about 316 kg. What matters is not only the sum but how it is delivered: not evenly over the roof, but as point forces through the hooks straight into the rafters. Snow and wind on the panels also pass through the hooks, so the engine calculates the force on each one.
What snow and wind loads apply in Lviv?
Values from DBN V.1.2-2:2006 with Amendments 1 and 2, annex E, for the regional centre. Check them against the map for the actual address; the snow and wind calculator gives the same figures.
| Quantity | Formula and clause | Value |
|---|---|---|
| S0 / W0 | annex E, Lviv | 1310 / 520 Pa |
| Snow shape coefficient μ at 35° | annex Zh, scheme 1: 1 up to 25°, 0 from 60°, linear between | 0.71 |
| Snow on the horizontal projection Sm | γfm · S0 · Calt · μ, Ce = 1 | 936 Pa |
| Snow on the slope | Sm · cos² α | 628 Pa |
| Exposure factor c_e at 7 m | EN 1991-1-4, 4.5, terrain II | 2.13 |
| Wind Wm for EN coefficients | γfm · W0 · c_e(z) · Calt | 1108 Pa |
| Coefficient Ch at 7 m | table 9.01, terrain II | 0.78 |
| Wind Wm,h for DBN coefficients | γfm · W0 · Ch · Calt | 406 Pa |
| Hook uplift coefficient c_p | 1.30 on Wm (reference value, clause 9.8) or 2.00 on Wm,h (edge strip e/10 = 700 mm, clause 9.16), the larger uplift | 1.30 |
| Windward slope coefficient c_e1 | annex I, scheme 2 | +0.19 |
| Wind pressing down W↓ | c_e1 · Wm,h | 76 Pa |
Two wind pressures appear because each coefficient keeps its own basis. The coefficients of EN 1991-1-4 are defined on the peak pressure, so they take Wm with the EN exposure factor c_e(z); W0 (the mean 50-year pressure at 10 m, clause 9.6) is taken as the basic pressure q_b. DBN's own coefficients (clause 9.16, annex I) go with Wm,h and the mean-wind factor Ch of table 9.01. The panel field reaches into the 700 mm edge strip, where clause 9.16 gives 2.00 · 406 = 812 Pa, but the reference 1.30 for panels parallel to the roof gives 1.30 · 1108 = 1440 Pa, so the EN value governs here. Snow, meanwhile, presses the panels down onto the roof.
What force does each hook take?
The engine checks two cases per hook, where A is the panel area, n the number of hooks, γn = 1.00:
| Case | Engine formula | Result |
|---|---|---|
| Uplift | γn · c_p · Wm · A / n | 1860 N |
| Pressure | γn · (1.05 · 120 + max(S + 0.9 · W↓, W↓ + 0.9 · S)) · A / n | 1062 N |
Here S = 628 Pa and the design load in the brackets is about 822 Pa. There are 20 hooks: 4 rails of 5. The reference capacity for metal tile is 3.0 kN uplift and 2.5 kN pressure, so utilisation is 62 % and 42 %. These are the calculator's reference values; for a real hook use the manufacturer's data sheet.
Rail: aluminium 40 x 40, span 900 mm, load strip 1139 mm, q_d = 0.936 N/mm, M = 0.09 kN·m. Strength 17 %, deflection against L/200 10 %.
How many hooks, and what rafter spacing?
Hooks sit only on rafters, so their number follows the rafter spacing and not just the panels. The fewer the hooks, the more force on each.
| Variant | Hooks | Uplift, N | Pressure, N | Rail, strength / deflection |
|---|---|---|---|---|
| Rafters at 600 mm | 36 | 1033 | 590 | 8 % / 3 % |
| Rafters at 900 mm, 2 rails per row | 20 | 1860 | 1062 | 17 % / 10 % |
| Rafters at 900 mm, 3 rails per row | 30 | 1240 | 708 | 11 % / 7 % |
| Rafters at 1200 mm | 16 | 2325 | 1327 | 30 % / 24 % |
Rafters at 900 mm give 1.8 times the force per hook of rafters at 600 mm, and a third rail per row cuts it by a third. This is only about the hooks: whether the rafter itself holds, this table does not say.
How does the roof pitch change the loads?
| Pitch | μ | Sm, Pa | Uplift, N | Pressure, N | Pressure of 2.5 kN |
|---|---|---|---|---|---|
| 25° | 1.00 | 1310 | 1860 | 1553 | 62 % |
| 35° | 0.71 | 936 | 1860 | 1062 | 42 % |
| 45° | 0.43 | 561 | 1860 | 738 | 30 % |
Uplift does not depend on the pitch because c_p is fixed in the engine. Pressure at 25° is 46 % higher: snow slides less, and the wind no longer presses down (c_e1 is not positive). On a low-pitch roof in Lviv snow governs. For a roof from 25° with an eave up to 500 mm the engine recommends snow guards.
What does the engine check, and what does it not?
The report has three parts: the loads per DBN, the roof attachments (uplift and pressure per hook), the rail (strength and deflection). That is enough to say the mounting system holds on its supports.
The engine does not calculate:
- Rafters and purlins. Their section, spacing, span, timber species and grade, and moisture are unknown to it. The force of 4 hooks of 1.06 kN on each of the 5 rafters used (4.25 kN) is a load on the rafter that an engineer checks.
- The condition of the structure. Rot, beetle, deflection, weakened joints, rafters cut earlier.
- The battens and the covering. The hooks go into the rafter, but the covering must bear the pressure and not leak at the holes.
- The real capacity of the hook. 3.0 and 2.5 kN are reference values.
- Snow pockets, and snow sliding off the panels onto a lower roof or an entrance.
- Permits. For a detached, garden or holiday house, a rooftop PV system needs no permit documents, and a structural survey is at the owner's discretion (CMU Resolution No. 77 of 28.01.2026). The engine recommends checking the load capacity of the roof.
What to measure on the roof before the quote
- Rafters: section (width and height), centre-to-centre spacing, timber species if known. The spacing goes into the calculator.
- Rafter span: the distance between supports, meaning the wall plate, purlin, ridge, strut. A long span with no intermediate support is one of the main reasons to call an engineer.
- Condition: rot, beetle, signs of leaks, sag, cracks. Sag shows along the ridge and eave lines.
- Covering: type, age, batten spacing, condition of the sheets. Cracked slate or worn metal tile should be replaced before installation.
- Geometry: pitch (inclinometer), slope and eave length, ridge height, setbacks.
- Access: can you get into the attic and see the rafter from below.
When to call a structural engineer
- Rafters thinner or more widely spaced than typical, or their section is unknown.
- Visible sag, rot, beetle, traces of old repairs.
- Rafters over a long span with no intermediate support.
- A low-pitch roof with heavy snow, where the pressure on the hooks grows (62 % at 25°).
- An old roof getting more than a few panels.
- The customer or the insurer asks for a survey document.
The engine's hook calculation is the first step. It does not replace an engineer's conclusion about the roof.
FAQ
Will an ordinary roof carry solar panels?
Often yes: 10 panels (25.83 m²) add 3.10 kN, about 12 kg per m² of panel area. But the answer comes from the rafter section and condition, not from a general rule, so measure the roof and show it to an engineer when in doubt.
What load do solar panels put on a roof?
The engine takes 120 Pa on the panel area. For 10 panels of 2278 x 1134 mm that is 3.10 kN. Snow and wind come on top: in Lviv, 628 Pa of snow on the slope, and 1860 N uplift and 1062 N pressure on each of the 20 hooks.
Do I need a design to install PV on a private house?
For a detached house no permit is needed (CMU Resolution No. 77 of 28.01.2026), but checking the load capacity of the roof is recommended. The attachments calculator gives a preliminary hook calculation, and a full design with drawings can be made in the Solispec designer.
What hook spacing for metal tile?
A multiple of the rafter spacing and no more than the limit for the covering. At 900 mm rafters and two rails per row the engine gives 20 hooks, at 600 mm 36. Details of the metal-tile detail are on the metal tile mounting page, and an overview is in the roof mounting article.
This is a preliminary calculation; a qualified structural engineer checks it before installation. The loads are per DBN V.1.2-2:2006 with Amendments 1 and 2. The engine compared with a hand calculation is on the calculation check page, a sample report on the samples page. Snow and wind for the city are on the Lviv page.