Solar carport for 2 cars near Rzeszów: loads and steel

A steel two-car carport with PV panels on top in Polish snow zone 3 and wind zone 1. Snow and wind from the national annex, EN 1990 combinations, purlins, rafters, posts, footing uplift and the steel list.

Von Solispec editorial9 Min. Lesezeit

Dieser Text ist noch nicht übersetzt — das Original wird angezeigt.

A steel two-car solar carport near Rzeszów is 12 modules of 580 W (6.96 kWp) on 3 frames at 3050 mm and 6 posts. With s_k = 1200 Pa and q_b = 300 Pa every member passes, the footing (64 %) and rafter (62 %) most. A C 60 x 40 x 2 purlin failed. The calculation is preliminary.

The question came from a YouTube channel author who is building a 5 x 6 m timber carport with a 50 degree gable roof in Tarnobrzeg and asked about the loads. The Solispec engine designs steel structures, so below we work through a steel carport with panels on the roof. Timber has different strengths, joints and moisture effects: such a carport needs a separate check by a structural engineer.

Snow and wind: Rzeszów and Tarnobrzeg

Values entered per the national annex from the Solispec city data. Rzeszów is on the city list of the snow and wind calculator and gives the same figures there:

RzeszówTarnobrzeg
Snow / wind zone3 / 13 / 1
Altitude, m209162
s_k, Pa (PN-EN 1991-1-3 + NA)12001200
q_b, Pa (PN-EN 1991-1-4 + NA)300300
Nearest zone boundarysnow zone 2: 3.3 km; wind zone 3: 9.8 kmsnow zone 2: 1.6 km

In zone 3, s_k = max(1.2; 0.006 A − 0.6) kN/m², and at 209 m the minimum of 1.2 governs. In wind zone 1 below 300 m, q_b = 0.30 kN/m². Both towns give the same figures, so the calculation below holds for Tarnobrzeg too. The zone boundaries are close, though: read the plot's zone from the annex map, not from the town's name.

The carport

The engine has no separate carport mode. The closest is its ground table with concrete footings: a frame of a rafter on two posts, with purlins along the table. In it we raise the lower panel edge to 2200 mm and space the frames so that a car fits between them.

  • Module: LONGi Hi-MO 6 LR5-72HTH-580M, 580 W, 2278 x 1134 mm. 12 modules, landscape, 4 rows of 3: 6.96 kWp.
  • Monopitch roof at 15 degrees. The slope is 4596 mm long, the table 6874 mm.
  • Lower panel edge 2200 mm, upper 3423 mm above the ground.
  • 3 frames at 3050 mm, i.e. two parking bays, each between two frames. 6 posts in all.
  • Purlins: tube 60 x 60 x 2, 3 per panel row. Rafter: C 100 x 50 x 2.5. Posts: tube 60 x 60 x 2.
  • Footing under each post: concrete Ø350 mm, 1300 mm deep, 0.125 m³ per post.

Loads step by step

QuantityFormula and clauseValue
Partial factor γ_Q, snow / windEN 1990, table A1.2(B)1.50 / 1.50
Snow shape coefficient μ at 15°EN 1991-1-3, table 5.20.80
Design snow on the plan Sγ_Q · μ · s_k, C_e = C_t = 11440 Pa
Exposure factor c_e(z)EN 1991-1-4, 4.5, terrain II, z = 3.4 m1.71
Design wind pressure Wγ_Q · c_e(z) · q_b771 Pa
Canopy force coefficient c_f, uplift / downwardEN 1991-1-4, table 7.6, φ = 01.10 / 0.70
Combination for the purlin1.35 · G + S + 0.6 · W↓ (EN 1990 (6.10), ψ_0 from table A1.1)

The engine gives μ = 0.80 from 15 to 30 degrees, so at 15 degrees the snow does not slide off in the calculation: 0.8 · 1200 · 1.5 = 1440 Pa. Wind grows with height: at 3.4 m the factor c_e gives 771 Pa against the basic 300 Pa. For a monopitch canopy table 7.6 gives separate coefficients for uplift (1.10) and downward pressure (0.70).

Three tries at the purlin

First the engine got the table in its default layout: modules in portrait, 2 rows of 5, a C 60 x 40 x 2 purlin, two purlins per row. The result was critical.

VariantFrame stepPurlin, strengthPurlin, deflection (L/200)
2 x 5 portrait, C 60 x 40 x 2, 2 purlins per row2560 mm136 %182 %
4 x 3 landscape, C 60 x 40 x 2, 3 purlins per row3050 mm64 %102 %
4 x 3 landscape, tube 60 x 60 x 2, 3 purlins per row3050 mm41 %65 %

The default maximum frame step of a ground table is 2000 mm. A carport needs room for a car between frames, here 3050 mm, and the purlin grows with the span squared (moment) and to the fourth power (deflection). Landscape modules with three purlins per row cut the load strip of one purlin to 378 mm. The 60 x 60 x 2 tube (W = 8380 mm³) gives the rest of the margin. Variant 2 shows that on a carport deflection governs, not strength.

Members and utilisation

CheckEngine calculationUtilisation
Purlin, strengthq_d = 0.691 N/mm, M = q·L²/8 = 0.80 kNm at L = 3050 mm41 %
Purlin, deflectionagainst L/20065 %
Rafter C 100 x 50 x 2.55.58 N/mm from the purlins, M = 2.27 kNm; span between posts 2492 mm, overhang 902 mm62 %
Rear post, compressionN = 15.39 kN, slenderness λ = 130, N_b,Rd = 38.0 kN41 %
Footing, uplift8.61 kN against 13.42 kN holding force64 %
Embedment against frost1.00 m against 1.30 mok

The posts stand at 23 % and 77 % of the slope length from the bottom. The front post is 2366 mm above the ground, the rear one 3011 mm, and 2407 mm apart in plan. The rear post is slender (λ = 130), so the engine asks for bracing in both planes: a knee brace in the frame and a cross between the rear posts.

Posts and footings

The uplift on the front post is 0.75 F_z, where F_z = γn · c_f · W · A · cos α is the vertical wind force on the frame. With c_f = 1.10 it comes to 8.61 kN. The holding force of the Ø350 x 1300 footing is 0.9 of the concrete weight plus soil friction on the side: 13.42 kN, an estimate. The frost depth of 1.00 m is zone II of the PN-81/B-03020 map, which the engine uses as a guide. Verify it against local data.

With screw piles the same 8.61 kN becomes the pull-out requirement of the pile. The engine does not compute the pile capacity: it comes from a soil report or a pull-out test on the plot.

Steel list from the engine

ItemSectionQuantity x cut length
Front posttube 60 x 60 x 23 x 3691 mm (1300 mm in concrete)
Rear posttube 60 x 60 x 23 x 4336 mm
RafterC 100 x 50 x 2.53 x 4296 mm
Rear / front knee bracetube 60 x 60 x 23 x 2769 mm / 3 x 3215 mm
Cross between rear poststube 60 x 60 x 24 x 3877 mm
Purlinstube 60 x 60 x 212 lines from pieces of 6000 mm and 1014 mm, 12 splices

In total 154.6 m of profile from 29 bars of 6000 mm, 0.83 m³ of concrete with a 10 % margin, 24 end clamps and 24 middle clamps. The frame nodes have 2 M10 class 8.8 bolts each: the engine counts their sets (among them 12 x M10 x 150 post to rafter and 44 x M10 x 200 through spacers). In this mode the report gives no shear and bearing utilisation for the frame node bolts; a structural engineer checks that.

What a 50 degree gable roof changes

The carport in the question has a 50 degree roof. For a 50 degree slope the engine gives μ = 0.27 instead of 0.80, a design snow of 480 Pa on the plan instead of 1440 Pa. Snow largely slides off such a roof, but it lands at the eaves, on a car or a path. Wind works the other way: a steep roof is taller and catches more wind, so pressure and suction grow, and anchorage and bracing matter more than purlins. We give no wind figures for 50 degrees here: table 7.6 for canopies stops at 30 degrees, and for timber the engineer calculates anyway.

What this calculation leaves out

  • Blockage under the roof. The engine takes φ = 0 (empty underneath). Cars and stored items are blockage, for which table 7.6 has a separate uplift row. The engineer checks it.
  • Horizontal force on the post, bearing pressure under the footing, a car hitting a post. The report does not give them.
  • Clearance. 2200 mm is the lower panel edge. The steel under it is lower by the purlin and rafter depth; measure the clearance on the drawing.
  • Drifts and snow from a higher roof. A carport next to a building gets a drift.
  • Timber. Materials and joints other than the steel in the engine's catalogue.

Checklist

  1. Read the plot's snow and wind zone from the annex map and enter s_k and q_b in the snow and wind calculator.
  2. Set the frame step for the cars, then check the purlin: on a carport deflection governs.
  3. Check that the report has no critical items. Here it has none.
  4. Read the footing line: uplift against holding force, embedment against frost depth.
  5. Settle the clearance, post guards and the blockage under the roof.
  6. Have a qualified structural engineer check the result.

A comparison of the engine with a hand calculation is on the calculation check page, a sample report with drawings and a cut list on the samples page. The ground table with its other options is described in ground mounting. Your own carport can be worked through in the Solispec designer.

This is a preliminary calculation; a qualified structural engineer checks it before installation. Loads are values entered per the national annex, design values per EN 1990.

FAQ

What snow load applies to a carport in Rzeszów or Tarnobrzeg?

Both towns are in snow zone 3: s_k = 1200 Pa. With a 15 degree roof μ = 0.80 and the design snow on the plan is 1440 Pa. The zone 2 boundary is a few kilometres away, so check the plot's zone on the map.

What frame step does a two-car carport need?

Here 3 frames at 3050 mm. At that step a C 60 x 40 x 2 purlin fails on deflection (102 %), and a 60 x 60 x 2 tube passes (65 %).

Does snow stop mattering on a 50 degree roof?

It drops to μ = 0.27, 480 Pa instead of 1440 Pa, but wind grows and snow slides off at the eaves. For a steep timber roof the loads and joints are calculated by a structural engineer.

TragwerkeNormen

Neuigkeiten und Planungstipps

Was es Neues bei Solispec gibt, Änderungen der Normen und praktische Tipps zur Planung von Solaranlagen.

Was Sie interessiert

Wie wir Ihre Daten verarbeiten: Datenschutzerklärung.

Planer für Freiflächen-Unterkonstruktionen

Planen Sie die Freiflächen-Unterkonstruktion Ihrer Solaranlage

Solispec wählt Profile und Pfosten, prüft die Konstruktion gegen Schnee und Wind und kalkuliert sie bis zur letzten Schraube.

  • Ohne Registrierung
  • Prüfung auf Schnee und Wind
  • Zeichnungen und Kostenvoranschlag